4-16 Torque Limit Motor Mode
Range:
Function:
110.0 %* [0.0 - 1000.0 %]
Enter the maximum torque limit for motor operation. The torque limit is active in the speed range
up to and including the rated motor speed set in par.1-25
. To protect the
motor from reaching the stalling torque, the default setting is 1.1 x the rated motor torque (calcu-
lated value). See also par.14-25
for further details.
If a setting in par.1-00
to par.1-28
is not automatically reset to the default setting.
4-17 Torque Limit Generator Mode
Range:
Function:
100.0 %* [0.0 - 1000.0 %]
Enter the maximum torque limit for generator mode operation. The torque limit is active in the speed
range up to and including the rated motor speed (par.1-25
). Refer to par.
for further details.
If a setting in par.1-00
to par.1-28
is not automatically reset to the default settings.
4-18 Current Limit
Range:
Function:
110.0 %* [1.0 - 1000.0 %]
Enter the current limit for motor and generator operation. To protect the motor from reaching stall-
ing torque, the default setting is 1.1 x the rated motor current (set in par. 1-24). If a setting in par.
1-00 to par. 1-26 is changed, par.4-16
are not
automatically reset to the default settings.
4-19 Max Output Frequency
Range:
Function:
100.0 Hz* [1.0 - 1000.0 Hz]
Enter the maximum output frequency value. par.4-19
specifies the absolute
limit on the adjustable frequency drive output frequency for improved safety in applications where
accidental overspeeding must be avoided. This absolute limit applies to all configurations and is
independent of the setting in par.1-00
. This parameter cannot be adjusted while
the motor is running.