[2]
Initialization
Select
Initialization
[2] to reset all parameter values to default settings, except for par.15-03
and par.15-05
. The adjustable frequency drive will reset
during the next power-up.
par.14-22
will also revert to the default setting
Normal operation
[0].
[3]
Boot mode
14-25 Trip Delay at Torque Limit
Range:
Function:
60 s*
[0 - 60 s]
Enter the torque limit trip delay in seconds. When the output torque reaches the torque limits (par.
4-16
), a warning is triggered.
When the torque limit warning has been continuously present for the period specified in this pa-
rameter, the adjustable frequency drive trips. Disable the trip delay by setting the parameter to 60
s = OFF. Thermal adjustable frequency drive monitoring will still remain active.
14-26 Trip Delay at Inverter Fault
Range:
Function:
0. s*
[0 - 35 s]
When the adjustable frequency drive detects an overvoltage in the set time, tripping will be affected
after the set time.
14-29 Service Code
Range:
Function:
0 N/A*
[-2147483647 - 2147483647 N/A] Service use only.
VLT
®
HVAC Drive Programming Guide
3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-139
3