21-53 Ext. 3 Reference Source
Option:
Function:
See par.21-13
for details.
[0] *
No function
[1]
Analog input 53
[2]
Analog input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
Digital pot.meter
[21]
Analog input X30/11
[22]
Analog input X30/12
[23]
Analog Input X42/1
[24]
Analog Input X42/3
[25]
Analog Input X42/5
[30]
Ext. Closed-loop 1
[31]
Ext. Closed-loop 2
[32]
Ext. Closed-loop 3
21-54 Ext. 3 Feedback Source
Option:
Function:
See par.21-14
for details.
[0] *
No function
[1]
Analog input 53
[2]
Analog input 54
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[100]
Bus feedback 1
[101]
Bus feedback 2
[102]
Bus feedback 3
21-55 Ext. 3 Setpoint
Range:
Function:
0.000 Ex-
tPID3Unit*
[par. 21-51 - par. 21-52 Ex-
tPID3Unit]
See par.21-15
for details.
21-57 Ext. 3 Reference [Unit]
Range:
Function:
0.000 Ex-
tPID3Unit*
[-999999.999 - 999999.999 Ex-
tPID3Unit]
See par.21-17
for details.
3 Parameter Description
VLT
®
HVAC Drive Programming Guide
3-194
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark