10-15 Net Control
Read only from LCP
Option:
Function:
Select the control source in Instance 21/71 and 20/70.
[0] *
Off
Enables control via analog/digital inputs.
[1]
On
Enable control via the serial communication bus.
3.11.4 10-2* COS Filters
Parameters for configuring COS filter settings.
10-20 COS Filter 1
Range:
Function:
0 N/A*
[0 - 65535 N/A]
Enter the value for COS Filter 1 to set up the filter mask for the status word. When operating in COS
(Change-Of-State), this function filters out bits in the status word that should not be sent if they
change.
10-21 COS Filter 2
Range:
Function:
0 N/A*
[0 - 65535 N/A]
Enter the value for COS Filter 2, to set up the filter mask for the Main Actual Value. When operating
in COS (Change-Of-State), this function filters out bits in the Main Actual Value that should not be
sent if they change.
10-22 COS Filter 3
Range:
Function:
0 N/A*
[0 - 65535 N/A]
Enter the value for COS Filter 3, to set up the filter mask for PCD 3. When operating in COS (Change-
Of-State), this function filters out bits in PCD 3 that should not be sent if they change.
10-23 COS Filter 4
Range:
Function:
0 N/A*
[0 - 65535 N/A]
Enter the value for COS Filter 4 to set up the filter mask for PCD 4. When operating in COS (Change-
Of-State), this function filters out bits in PCD 4 that should not be sent if they change.
3.11.5 10-3* Parameter Access
Parameter group providing access to indexed parameters and defining programming set-up.
10-30 Array Index
Range:
Function:
0 N/A*
[0 - 255 N/A]
View array parameters. This parameter is valid only when a DeviceNet serial communication bus is
installed.