
26-10 Terminal X42/1 Low Voltage
Range:
Function:
0.07 V*
[0.00 - par. 6-31 V]
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value set in par.26-14
Term. X42/1 Low Ref./Feedb. Value
26-11 Terminal X42/1 High Voltage
Range:
Function:
10.00 V*
[par. 6-30 - 10.00 V]
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par.26-15
Term. X42/1 High Ref./Feedb. Value
26-14 Term. X42/1 Low Ref./Feedb. Value
Range:
Function:
0.000 N/A* [-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the low voltage value set in par.
26-10
26-15 Term. X42/1 High Ref./Feedb. Value
Range:
Function:
100.000 N/
A*
[-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the high voltage value set in par.
26-11
.
26-16 Term. X42/1 Filter Time Constant
Range:
Function:
0.001 s*
[0.001 - 10.000 s]
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
noise in terminal X42/1. A high time constant value improves dampening but also increases the time
delay through the filter. This parameter cannot be adjusted while the motor is running.
26-17 Term. X42/1 Live Zero
Option:
Function:
This parameter makes it possible to enable the live zero monitoring, for example where the analog
input is a part of the adjustable frequency drive control, rather than being used as part of a decentral
I/O system, such as a building management system.
[0]
Disabled
[1] *
Enabled
26-20 Terminal X42/3 Low Voltage
Range:
Function:
0.07 V*
[0.00 - par. 6-31 V]
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value set in par.26-24
Term. X42/3 Low Ref./Feedb. Value
26-21 Terminal X42/3 High Voltage
Range:
Function:
10.00 V*
[par. 6-30 - 10.00 V]
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par.26-25
Term. X42/3 High Ref./Feedb. Value
26-24 Term. X42/3 Low Ref./Feedb. Value
Range:
Function:
0.000 N/A* [-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the low voltage value set in par.
26-20
VLT
®
HVAC Drive Programming Guide
3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-253
3