9-70 Programming Set-up
Option:
Function:
Select the set-up to be edited.
[0]
Factory setup
Uses default data. This option can be used as a data source to return the other set-ups to a known
state.
[1]
Set-up 1
Edits Set-up 1.
[2]
Set-up 2
Edits Set-up 2.
[3]
Set-up 3
Edits Set-up 3.
[4]
Set-up 4
Edits Set-up 4.
[9] *
Active Set-up
Follows the active set-up selected in par.0-10
This parameter is unique to LCP and serial communication busses. See also par.0-11
9-71 Profibus Save Data Values
Option:
Function:
Parameter values changed via Profibus are not automatically stored in non-volatile memory. Use
this parameter to activate a function that stores parameter values in the EEPROM non-volatile
memory, so changed parameter values will be retained at power-down.
[0] *
Off
Deactivates the non-volatile storage function.
[1]
Store edit setup
[2]
Store all setups
Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
9-72 ProfibusDriveReset
Option:
Function:
[0] *
No action
[1]
Power-on reset
Resets the adjustable frequency drive upon power-up, as for power-cycle.
[3]
Comm option reset
Resets the Profibus option only, useful after changing certain settings in parameter group 9-**, e.g.,
par.9-18
When reset, the adjustable frequency drive disappears from the serial communication bus, which
may cause a communication error from the master.
9-80 Defined Parameters (1)
Array [116]
No LCP access
Read only
Range:
Function:
0 N/A*
[0 - 9999 N/A]
This parameter displays a list of all the defined adjustable frequency drive parameters available for
Profibus.
3 Parameter Description
VLT
®
HVAC Drive Programming Guide
3-108