130BP076.10
After the link is complete, par.0-13
will read {1,2} to indicate that all ‘not
changeable during operation’ parameters are now the same in Set-up 1 and Set-up 2. If there are
changes to a ‘not changeable during operation’ parameter, e.g. par.1-30
Set-up 2, they will also be changed automatically in Set-up 1. A switch between Set-up 1 and Set-
up 2 during operation is now possible.
[0] *
Not linked
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
0-13 Readout: Linked Set-ups
Array [5]
Range:
Function:
0 N/A*
[0 - 255 N/A]
View a list of all the set-ups linked by means of par.0-12
. The parameter has
one index for each parameter set-up. The parameter value displayed for each index represents
which set-ups are linked to that parameter set-up.
Index
LCP value
0
{0}
1
{1,2}
2
{1,2}
3
{3}
4
{4}
Table 3.2: Example: Set-up 1 and Set-up 2 are linked
0-14 Readout: Prog. Set-ups / Channel
Range:
Function:
0 N/A*
[-2147483648 - 2147483647 N/A] View the setting of par.0-11
for each of the four different communication
channels. When the number is displayed in hex, as it is in the LCP, each number represents one
channel.
Numbers 1-4 represent a set-up number; ‘F’ means factory setting; and ‘A’ means active set-up.
The channels are, from right to left: LCP, Adjustable Frequency Drive bus, USB, HPFB1.5.
Example: The number AAAAAA21h means that the Adjustable Frequency Drive bus selected Set-up
2 in par.0-11
, the LCP selected Set-up 1 and all others used the active set-up.