1-03 Torque Characteristics
Option:
Function:
[0]
Compressor torque
Compressor
[0]: For speed control of screw and scroll compressors. Provides a voltage which is
optimized for a constant torque load characteristic of the motor in the entire range down to 10 Hz.
[1]
Variable torque
Variable Torque
[1]: For speed control of centrifugal pumps and fans. Also to be used when con-
trolling more than one motor from the same adjustable frequency drive (e.g., multiple condenser
fans or cooling tower fans). Provides a voltage which is optimized for a squared torque load char-
acteristic of the motor.
[2]
Auto Energy Optim. CT
Auto Energy Optimization Compressor
[2]: For optimum energy efficient speed control of screw and
scroll compressors. Provides a voltage which is optimized for a constant torque load characteristic
of the motor in the entire range down to 15Hz, but in addition, the AEO feature will adapt the voltage
exactly to the current load situation, thereby reducing energy consumption and audible noise from
the motor. To obtain optimal performance, the motor power factor cos phi must be set correctly.
This value is set in par.14-43
. The parameter has a default value which is automat-
ically adjusted when the motor data is programmed. These settings will typically ensure optimum
motor voltage but if the motor power factor cos phi requires tuning, an AMA function can be carried
out using par.1-29
Automatic Motor Adaptation (AMA)
. It is very rarely necessary to adjust the motor
power factor parameter manually.
[3] *
Auto Energy Optim. VT
Auto Energy Optimization VT
[3]: For optimum energy efficient speed control of centrifugal pumps
and fans. Provides a voltage which is optimized for a squared torque load characteristic of the motor
but in addition the AEO feature will adapt the voltage exactly to the current load situation, thereby
reducing energy consumption and audible noise from the motor. To obtain optimal performance,
the motor power factor cos phi must be set correctly. This value is set in par.14-43
The parameter has a default value and is automatically adjusted when the motor data is program-
med. These settings will typically ensure optimum motor voltage but if the motor power factor cos
phi requires tuning, an AMA function can be carried out using par.1-29
. It is very rarely necessary to adjust the motor power factor parameter manually.
3.3.2 1-2* Motor Data
Parameter group 1-2* comprises input data from the nameplate on the connected motor.
Parameters in parameter group 1-2* cannot be adjusted while the motor is running.
NOTE!
Changing the value of these parameters affects the setting of other parameters.
1-20 Motor Power [kW]
Range:
Function:
4.00 kW*
[0.09 - 3000.00 kW]
Enter the nominal motor power (in kW) according to the motor nameplate data. The default value
corresponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running. Depending on the choices made in
par.0-03
is made
invisible.
VLT
®
HVAC Drive Programming Guide
3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-19