8-72 MS/TP Max Masters
Range:
Function:
127 N/A*
[0 - 127 N/A]
Define the address of the master which holds the highest address in this network. Decreasing this
value optimizes polling for the token.
NOTE!
This parameter is active only when par.8-30
Adjustable Frequency Drive Option
.
8-73 MS/TP Max Info Frames
Range:
Function:
1 N/A*
[1 - 65534 N/A]
Define how many info/data frames the device is allowed to send while holding the token.
NOTE!
This parameter is active only when par.8-30
Adjustable Frequency Drive Option
.
8-74 "Startup I am"
Option:
Function:
[0] *
Send at power-up
[1]
Continuously
Choose whether the device should send the "I-Am" service message only at power-up or continu-
ously with an interval of approx. 1 min.
NOTE!
This parameter is active only when par.8-30
Adjustable Frequency Drive Option
.
8-75 Initialization Password
Range:
Function:
0 N/A*
[0 - 0 N/A]
Enter the password needed for execution of Drive Re-initialization from BACnet.
NOTE!
This parameter is active only when par.8-30
Adjustable Frequency Drive Option
.
3.9.7 8-8* Adjustable Frequency Drive Port Diagnostics
These parameters are used for monitoring the bus communication via the Adjustable Frequency Drive Port.
8-80 Bus Message Count
Range:
Function:
0 N/A*
[0 - 0 N/A]
This parameter shows the number of valid messages detected on the bus.