14-62 Inv. Overload Derate Current
Range:
Function:
95 %*
[50 - 100 %]
Defines the desired current level (in % of rated output current for the adjustable frequency drive)
when running with reduced pump speed after load on the adjustable frequency drive has exceeded
the allowable limit (110% for 60 sec.).
3.15 Main Menu - Adjustable Frequency Drive Information - Group 15
3.15.1 15-** Drive Information
Parameter group containing adjustable frequency drive information such as operating data, hardware configuration and software versions.
3.15.2 15-0* Operating Data
Parameter group containing operating data, such as operating hours, kWh counters, power-ups, etc.
15-00 Operating Hours
Range:
Function:
0 h*
[0 - 2147483647 h]
View how many hours the adjustable frequency drive has run. The value is saved when the adjust-
able frequency drive is turned off.
15-01 Running Hours
Range:
Function:
0 h*
[0 - 2147483647 h]
View how many hours the motor has run. Reset the counter in par.15-07
. The value is saved when the adjustable frequency drive is turned off.
15-02 kWh Counter
Range:
Function:
0 kWh*
[0 - 2147483647 kWh]
Registering the power consumption of the motor as a mean value over one hour. Reset the counter
in par.15-06
15-03 Power-ups
Range:
Function:
0 N/A*
[0 - 2147483647 N/A]
View the number of times the adjustable frequency drive has been powered up.
15-04 Over Temps
Range:
Function:
0 N/A*
[0 - 65535 N/A]
View the number of adjustable frequency drive temperature faults which have occurred.
15-05 Over Volts
Range:
Function:
0 N/A*
[0 - 65535 N/A]
View the number of adjustable frequency drive overvoltages which have occurred.