8-06 Reset Control Timeout
Option:
Function:
This parameter is active only when the choice
Hold set-up
[0] has been selected in par.8-05
[0] *
Do not reset
Retains the set-up specified in par.8-04
, [Select set-up 1-4] following a
control timeout.
[1]
Do reset
Returns the adjustable frequency drive to the original set-up following a control word timeout. When
the value is set to
Do reset
[1], the adjustable frequency drive performs the reset and then imme-
diately reverts to the
Do not reset
[0] setting.
8-07 Diagnosis Trigger
Option:
Function:
This parameter has no function for LonWorks.
[0] *
Disable
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
3.9.3 8-1* Ctrl. Word Settings
Parameters for configuring the option control word profile.
8-10 Control Profile
Option:
Function:
Select the interpretation of the control and status words corresponding to the installed serial com-
munication bus. Only the selections valid for the serial communication bus installed in slot A will be
visible in the LCP display.
[0] *
FC profile
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
8-13 Configurable Status Word STW
Option:
Function:
This parameter enables configuration of bits 12 – 15 in the status word.
[0]
No function
[1] *
Profile Default
Function corresponds to the profile default selected in par.8-10
[2]
Alarm 68 Only
Only set in case of an Alarm 68.
[3]
Trip excl Alarm 68
Set in case of a trip, except if the trip is executed by an Alarm 68.
[16]
T37 DI status
The bit indicates the status of terminal 37.
“0” indicates T37 is low (safe stop)
“1” indicates T37 is high (normal)
VLT
®
HVAC Drive Programming Guide
3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-93
3