25-27 Stage Function
Option:
Function:
If the stage function is set to
Disabled
[0], par.25-28
[0]
Disabled
[1] *
Enabled
25-28 Stage Function Time
Range:
Function:
15 s*
[0 - 300 s]
Stage function time is programmed to avoid frequent staging of the fixed speed pumps. The stage
function time starts if it is
Enabled
[1] by par.25-27
, and when the variable speed
pump is running at
Motor Speed High Limit
, with at least one fixed speed pump in the stop position. When
the programmed value of the timer expires, a fixed speed pump is staged.
25-29 Destage Function
Option:
Function:
The de-stage function ensures that the lowest number of pumps are running to save energy and to
avoid dead head water circulation in the variable speed pump. If the de-stage function is set to
Disabled
[0], the par.25-30
[0]
Disabled
[1] *
Enabled
25-30 Destage Function Time
Range:
Function:
15 s*
[0 - 300 s]
The de-stage function timer is programmable to avoid frequent staging/de-staging of the fixed
speed pumps. The de-stage function time starts when the adjustable speed pump is running at par.
4-11
, with one or more fixed
speed pumps in operation and system requirements satisfied. In this situation, the adjustable speed
pump contributes a little to the system. When the programmed value of the timer expires, a stage
is removed, avoiding dead head water circulation in the adjustable speed pump.