2.6 Control Terminals
Control terminals must be programmed. Each terminal has specific functions it is capable of per-
forming and a numbered parameter associated with it. See table below. The setting selected in
the parameter enables the function of the terminal.
It is important to confirm that the control terminal is programmed for the correct function.
Parameter settings are displayed by pressing
the [Status] key on the LCP.
130BP045.10
Use the arrow keys [
▲
], [
▼
], [
►
] and [
◄
] on
the LCP to scroll through parameters.
See the Programming Guide for details on changing parameters and the functions available for
each control terminal.
In addition, the input terminal must be receiving a signal. Confirm that the control and power
sources are wired to the terminal. Then check the signal.
Signals can be checked in two ways. Digital input can be selected for display by pressing [status]
key as discussed previously, or a voltmeter may be used to check for voltage at the control ter-
minal. See procedure details at Input Terminal Test in Section 6.
In summary, for proper adjustable frequency drive functioning, the adjustable fre-
quency drive input control terminals must be:
1.
wired properly
2.
powered
3.
programmed correctly for the intended function
4.
receiving a signal
2 Operator Interface and Adjustable Frequen-
cy Drive Control
High Power Service Manual for VLT
®
FC Series
Adjustable Frequency Drives
2-16
MG.90.L1.22 - VLT
®
is a registered Danfoss trademark
2
Содержание VLT HVAC FC 100
Страница 219: ......
Страница 220: ...Rev 2008 09 01 www danfoss com drives 130R0438 MG90L122 MG90L122 High Power Service Manual MG90L122...