A 3-pin test connector is located on the gate drive card near each gate signal lead. These are
labeled MK250, MK350, MK450, MK550, MK650, MK750, and, if the adjustable frequency drive is
equipped with a brake option, MK850 (see Figure 6-17).
For the sake of clarity, refer to the 3 pins as one, two, and three, reading left to right. Pins 1 and
2 of each connector are in parallel with the gate drive signal sent to the IGBTs. Pin 1 is the signal
and pin 2 is common.
7.
Reconnect AC power to the adjustable frequency drive.
8.
In stop mode, apply power to the adjustable frequency drive.
9.
Measure pins 1 and 2 of each test connector. Each reading should be approximately -9
VDC, indicating all IGBTs are turned off.
10.
Apply the run command to the adjustable frequency drive and 30 Hz reference.
11.
If using a DVM, measure pins 1 and 2 of each connector. Waveform to IGBTs is a square
wave that goes positive to 14 VDC and negative to -9 VDC. Average voltage read by DVM
should be 2.2 to 2.5 VDC.
130BX75.10
1
2
3
4
5
6
7
8
9
10
11 12
Figure 6.17: Gate Drive Card Test Connectors
1
Pin 1
7
MK450
2
MK850 (brake)
8
MK103 (V)
3
MK105 (brake option)
9
MK550
4
MK250
10
MK650
5
MK102 (U)
11
MK104 (W)
6
MK350
12
MK750
High Power Service Manual for VLT
®
FC Series
Adjustable Frequency Drives
6 Test Procedures
MG.90.L1.22 - VLT
®
is a registered Danfoss trademark
6-31
6