Standby
[Auto On] The adjustable frequency drive starts the motor using a start signal in a digital input (if
the parameter is programmed accordingly) or via serial communication.
Start delay
In par. 1-71
Start Delay
, the delay of the starting time was set. A Start command was activated
and the delay time is still running. The motor will start after the delay time has expired.
Start fwd/rev
Enable start forward
and
Enable start reverse
were selected as functions for two different digital
inputs (parameter group 5-1*). To start the motor, a direction dependent start signal has to be
given and the corresponding terminal has to be active.
Start inhibit
PROFIDrive profile
was selected in par. 8-10
Control Word Profile
. The start inhibition is active.
The adjustable frequency drive needs the first part (e.g., 0x047E) of the two-part start command
via serial communication to allow starting. See also operation status control ready.
Stop
[Off] was pressed on the LCP or Stop inverse was selected as a function for a digital input (Group
5-1*). The corresponding terminal is not active.
Trip
An alarm occurred. It is possible, provided the cause of the alarm is cleared, to reset the alarm
via a
Reset
signal ([Reset] key on the LCP, a control terminal or serial communication).
Trip lock
A serious alarm occurred. It is possible, provided the cause of the alarm was cleared, to reset the
alarm after line power has been switched off and on again. This can be done via a
reset
signal
([Reset] on the LCP, a control terminal or serial communication).
Unit/Drive not ready
PROFIDrive profile
was selected in par. 8-10
Control Word Profile
. A control word is sent to the
adjustable frequency drive via serial communication with Off 1, Off 2 and Off 3 active. Start inhibit
is active. To enable start, see operation status Start inhibit.
2 Operator Interface and Adjustable Frequen-
cy Drive Control
High Power Service Manual for VLT
®
FC Series
Adjustable Frequency Drives
2-12
MG.90.L1.22 - VLT
®
is a registered Danfoss trademark
2
Содержание VLT HVAC FC 100
Страница 219: ......
Страница 220: ...Rev 2008 09 01 www danfoss com drives 130R0438 MG90L122 MG90L122 High Power Service Manual MG90L122...