6.
Remove the soft charge resistor by removing the two mounting screws.
130BX83.10
1
2
Figure 7.10: D1/D3 Soft Charge Resistor (3 of 3)
380–480/500V: Clear wire leads.
525–690 V: Black wire leads.
1
Soft charge resistor
2
Mounting screws (Step 6)
Reassembly
1.
Clean the heatsink surface with a mild solvent or alcohol solution.
2.
Reassemble the remaining parts in reverse order of their removal. Tighten the T25 and
8 mm mounting screws to 2.3 Nm (20 in-lbs) and T30 and 10 mm to 4 Nm (35 in-lbs).
7 D-Frame Sizes Disassembly and Assembly
Instructions
High Power Service Manual for VLT
®
FC Series
Adjustable Frequency Drives
7-12
MG.90.L1.22 - VLT
®
is a registered Danfoss trademark
7