11. Note which gate lead connects to which SCR module. Ensure that the correct wire is
attached to the applicable SCR upon reassembly. Remove the wiring from each SCR
module. The connector is keyed for proper reinstallation. DO NOT force the connection.
12. Remove the SCR or diode module by removing the 4 retaining screws (T25) from
each module.
130BX107.10
1
2
3
4
5
6
7
8
Figure 8.10: SCR and Diode Modules (3 of 3)
1
SCR module SCR2
5
Diode module D1
2
Retaining screw (Step 12)
6
Diode module D2
3
SCR module SCR1
7
Diode module D3
4
SCR gate lead connection (Step 11)
8
SCR module SCR3
REASSEMBLY
Equipment Damage!
Do not reverse the SCR and diode modules during installation. Reversing the SCR
and diode modules can result in equipment damage.
NOTE!
For each AC input phase, there is one SCR module and one diode module. The SCR
is on the left, the diode on the right (as seen facing the upright unit). There are three
pairs. Only the SCR module has a connection pin for the gate signals.
1.
Replace SCR and diode modules in accordance with the instructions included with the
replacement modules.
2.
Reassemble in reverse order.
Attaching Hardware
Tightening Torque
T50
Per spare part instruction
T25
Per spare part instruction
17 mm
19 Nm (170 in-lbs)
13 mm
9.5 Nm (85 in-lbs)
10 mm
4 Nm (35 in-lbs)
8 mm
2.3 Nm (20 in-lbs)
8 E-Frame Sizes Disassembly and Assembly
Instructions
High Power Service Manual for VLT
®
FC Series
Adjustable Frequency Drives
8-12
MG.90.L1.22 - VLT
®
is a registered Danfoss trademark
8
Содержание VLT HVAC FC 100
Страница 219: ......
Страница 220: ...Rev 2008 09 01 www danfoss com drives 130R0438 MG90L122 MG90L122 High Power Service Manual MG90L122...