Ohm test of fans
1.
Measure between terminals 3 and 5 of power card connector MK107. It should read
approximately value D in Table 6-1.
Incorrect reading
For fans without an inductor, replace the fan. For adjustable frequency drives
with a fan and inductor, isolate the fault between the fan and the inductor as
follows.
1a
Disconnect CN3 and measure the resistance between pins 1 and 2 on the fan
side of the connector. Reading should be approx. 4 ohms. If incorrect, replace
fan.
1b
Disconnect CN4 and CN5. Measure the resistance across the inductor. Reading
should be less than 1 ohm. If incorrect, replace the inductor.
2.
Measure between terminals 11 and 13 of power card connector MK107. For units with
one top mounted fan, a reading of 400 ohms is expected. For units with two door moun-
ted fans, a reading of 200 ohms is expected.
Incorrect reading
For units with one top mounted fan, replace the fan. For units with two door mounted fans, isolate
the faulty fan as follows.
a.
Disconnect the wiring from the fan terminals.
b.
Read across the fan terminals on each fan. A reading of 400 ohms is expected. Replace
any defective fans.
Figure 6.11: Fan and DC Bus Fuse Locations
1
Power card
4
Mounting plate
2
DC bus fuse
5
MK107
3
Fan fuse
High Power Service Manual for VLT
®
FC Series
Adjustable Frequency Drives
6 Test Procedures
MG.90.L1.22 - VLT
®
is a registered Danfoss trademark
6-19