NOTICE!
The recommendations do not cover branch circuit
protection for UL.
Short-circuit protection
Danfoss recommends using the fuses/circuit breakers
mentioned in this section to protect service personnel and
property in case of component breakdown in the
adjustable frequency drive.
Overcurrent protection
The adjustable frequency drive provides overload
protection to limit threats to human life, property damage
and to avoid fire hazard due to overheating of the cables.
The adjustable frequency drive is equipped with an
internal overcurrent protection (
parameter 4-18 Current
Limit
) that can be used for upstream overload protection
(UL applications excluded). Moreover, fuses or circuit
breakers can be used to provide the overcurrent protection
in the installation. Overcurrent protection must always be
carried out according to national regulations.
The tables in this section list the recommended rated
current. Recommended fuses are of the type gG for small
to medium power sizes. For larger powers, aR fuses are
recommended. Use circuit breakers that meet the national/
international regulations and that limit the energy into the
adjustable frequency drive to an equal or lower level than
the compliant circuit breakers.
If fuses/circuit breakers are selected according to
recommendations, possible damage on the adjustable
frequency drive is mainly limited to damage inside the
unit.
Non-UL compliance
If UL/cUL is not to be complied with, use the following
fuses to ensure compliance with EN50178:
P110-P250
380–480 V
type gG
P315-P450
380–480 V
type gR
Table 4.11 EN50178 Fuses
UL Compliance
380–480 V, Enclosure types E and F
The fuses below are suitable for use on a circuit capable of
delivering 100,000 A
rms
(symmetrical), 240 V, or 480 V, or
500 V, or 600 V depending on the adjustable frequency
drive voltage rating. With the proper fusing, the adjustable
frequency drive Short Circuit Current Rating (SCCR) is
100,000 A
rms
.
Size/type
Bussmann
PN*
Rating
Ferraz
Siba
P315
170M4017
700 A, 700 V
6.9URD31D08A0700
20 610 32.700
P355
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
P400
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
P450
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
Table 4.12 Enclosure Types E, Electrical Fuses, 380–480 V
Size/type
Bussmann PN*
Rating
Siba
Internal Bussmann
option
P500
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P560
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P630
170M7082
2000 A, 700 V
20 695 32.2000
170M7082
P710
170M7082
2000 A, 700 V
20 695 32.2000
170M7082
P800
170M7083
2500 A, 700 V
20 695 32.2500
170M7083
P1M0
170M7083
2500 A, 700 V
20 695 32.2500
170M7083
Table 4.13 Enclosure Types F, Electrical Fuses, 380–480 V
Electrical Installation