Enclosure size size
E1
E2
F1
F2
F3
F4
315–450 kW
(425–600 hp) at
400 V
(380–480 V)
450–630 kW
(600–850 hp) at
690 V
(525–690 V)
315–450 kW
(425–600 hp) at
400 V
(380–480 V)
450–630 kW
(600–850 hp) at
690 V
(525–690 V)
500–710 kW
(650–950 hp) at
400 V
(380–480 V)
710–900 kW
(950–1200 hp) at
690 V
(525–690 V)
800–1000 kW
(1075–1350 hp)
at 400 V
(380–480 V)
1000–1200 kW
(1350–1600 hp)
at 690 V
(525–690 V)
500–710 kW
(650–950 hp) at
400 V
(380–480 V)
710–900 kW
(950–1200 hp) at
690 V
(525–690 V)
800–1000 kW
(1075–1350 hp)
at 400 V
(380–480 V)
1000–1400 kW
(1350–1875 hp)
at 690 V
(525–690 V)
IP
NEMA
21, 54
Type 1/Type 12
00
Chassis
21, 54
Type 1/Type 12
21, 54
Type 1/Type 12
21, 54
Type 1/Type 12
21, 54
Type 1/Type 12
Shipping
dimensions
[mm (in)]
Height
840 (33.1)
831 (32.72)
2324 (91.5)
2324 (91.5)
2324 (91.5)
2324 (91.5)
Width
2197 (86.5)
1705 (67.13)
1569 (61.77)
1962 (77.24)
2159 (85)
2559 (100.75)
Depth
736 (29)
736 (29)
1130 (44.5)
1130 (44.5)
1130 (44.5)
1130 (44.5)
Adjustable
frequency
drive
dimensions
[mm (in)]
Height
2000 (78.74)
1547 (60.91)
2204 (86.77)
2204 (86.77)
2204 (86.77)
2204 (86.77)
Width
600 (23.62)
585 (23.03)
1400 (55.12)
1800 (70.87)
2000 (78.74)
2400 (94.5)
Depth
494 (19.45)
498 (19.61)
606 (23.86)
606 (23.86)
606 (23.86)
606 (23.86)
Max.
weight
[kg
(lb)]
313 (690)
277 (611)
1004 (2214)
1246 (2747)
1299 (2864)
1541 (3397.4)
Table 3.3 Mechanical Dimensions, Enclosure Sizes E and F
3.2.6 Rated Power
Enclosure size
E1
E2
F1/F3
F2/F4
130BA818.10
130BA821.10
F3 F1
130BA959.10
F4 F2
130BB092.11
Enclosure
protection
IP
21/54
00
21/54
21/54
NEMA
Type 1/Type 12
Chassis
Type 1/Type 12
Type 1/Type 12
Normal overload
rated power -
110% overload
torque
315–450 kW (425–600
hp) at 400 V
(380–480 V)
450–630 kW (600–850
hp) at 690 V
(525–690 V)
315–450 kW (425–600
hp) at 400 V
(380–480 V)
450–630 kW (600–850
hp) at 690 V
(525–690 V)
500–710 kW (650–950 hp) at 400
V
(380–480 V)
710–900 kW (950–1200 hp) at
690 V
(525–690 V)
800–1000 kW (1075–1350 hp)
at 400 V
(380–480 V)
1000–1400 kW (1350–1875 hp)
at 690 V
(525–690 V)
Table 3.4 Rated Power, Enclosure Types E and F
NOTICE!
The F enclosures are available in four different sizes, F1, F2, F3 and F4. The F1 and F2 consist of an inverter cabinet on
the right and rectifier cabinet on the left. The F3 and F4 have an extra options cabinet left of the rectifier cabinet. The
F3 is an F1 with an extra options cabinet. The F4 is an F2 with an extra options cabinet.
Mechanical Installation
VLT
®
HVAC Drive FC 102
16
Danfoss A/S © 08/2014 All rights reserved.
MG11F522
3
3
Содержание VLT HVAC Drive FC 102
Страница 2: ......