Figure 6.11
3-15 Reference 1 Source
Option:
Function:
Select the reference input to be used
for the first reference signal.
Parameter 3-15 Reference 1 Source
,
parameter 3-16 Reference 2 Source
and
parameter 3-17 Reference 3 Source
define up to three different reference
signals. The sum of these reference
signals defines the actual reference.
[0]
No function
[1]
*
Analog Input 53
[2]
Analog Input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20] Digital pot.meter
[21] Analog input X30/11
[22] Analog input X30/12
[23] Analog Input X42/1
[24] Analog Input X42/3
[25] Analog Input X42/5
[29] Analog Input X48/2
[30] Ext. Closed-loop 1
[31] Ext. Closed-loop 2
[32] Ext. Closed-loop 3
NOTICE!
This parameter cannot be adjusted while the motor is
running.
3-16 Reference 2 Source
Option:
Function:
Select the reference input to be
used for the second reference signal.
parameter 3-15 Reference 1 Source
,
parameter 3-16 Reference 2 Source
and
parameter 3-17 Reference 3
Source
define up to three different
reference signals. The sum of these
reference signals defines the actual
reference.
[0]
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
*
Digital pot.meter
[21]
Analog input X30/11
[22]
Analog input X30/12
[23]
Analog Input X42/1
[24]
Analog Input X42/3
[25]
Analog Input X42/5
[29]
Analog Input X48/2
[30]
Ext. Closed-loop 1
[31]
Ext. Closed-loop 2
[32]
Ext. Closed-loop 3
NOTICE!
This parameter cannot be adjusted while the motor is
running.
4-10 Motor Speed Direction
Option:
Function:
Selects the motor speed direction required.
Use this parameter to prevent unwanted
reversing.
[0]
Clockwise
Only operation in clockwise direction is
allowed.
[2]
*
Both directions Operation in both clockwise and counter-
clockwise direction is allowed.
NOTICE!
The setting in
parameter 4-10 Motor Speed Direction
has
impact on the flying start in
How to Program
VLT
®
HVAC Drive FC 102
92