No.
Description
Warning
Alarm/trip
Alarm/trip lock
Parameter reference
96
Start delayed
X
22-7*
97
Stop delayed
X
22-7*
98
Clock fault
X
0-7*
201
Fire M was active
202
Fire M limits exceeded
203
Missing motor
204
Locked rotor
243
Brake IGBT
X
X
244
Heatsink temp
X
X
X
245
Heatsink sensor
X
X
246
Pwr.card supply
X
X
247
Pwr.card temp
X
X
248
Illegal PS config
X
X
250
New spare parts
X
251
New type code
X
X
Table 8.1 Alarm/Warning Code List
(X) Dependent on parameter.
1) Cannot be auto reset via parameter 14-20 Reset Mode.
A trip is the action when an alarm has appeared. The trip
coasts the motor and can be reset by pressing [Reset] or
by using the
Reset
function via a digital input (parameter
group
5-1* Digital Inputs
[1]). The original event that
caused an alarm cannot damage the adjustable frequency
drive or cause dangerous conditions. A trip lock is an
action when an alarm occurs, which may damage the
adjustable frequency drive or connected parts. A trip lock
situation can only be reset by power cycling.
Warning
yellow
Alarm
flashing red
Trip locked
yellow and red
Table 8.2 LED Indication
Alarm Word and Extended Status Word
Bit
Hex
Dec
Alarm Word
Warning Word
Extended Status Word
0
00000001
1
Brake Check
Brake Check
Ramping
1
00000002
2
Pwr. Card Temp
Pwr. Card Temp
AMA Running
2
00000004
4
Ground Fault
Ground Fault
Start CW/CCW
3
00000008
8
Ctrl.Card Temp
Ctrl.Card Temp
Slow-down
4
00000010
16
Ctrl. Word TO
Ctrl. Word TO
Catch Up
5
00000020
32
Overcurrent
Overcurrent
Feedback High
6
00000040
64
Torque Limit
Torque Limit
Feedback Low
7
00000080
128
Motor Th Over
Motor Th Over
Output Current High
8
00000100
256
Motor ETR Over
Motor ETR Over
Output Current Low
9
00000200
512
Inverter Overld.
Inverter Overld.
Output Freq High
10
00000400
1024
DC undervolt
DC undervolt
Output Freq Low
11
00000800
2048
DC overvolt
DC overvolt
Brake Check OK
12
00001000
4096
Short circuit
DC Voltage Low
Braking Max
13
00002000
8192
Soft-charge fault
DC Voltage High
Braking
14
00004000
16384
Line power ph. Loss
Line power ph. Loss
Out of Speed Range
15
00008000
32768
AMA Not OK
No Motor
OVC Active
16
00010000
65536
Live Zero Error
Live Zero Error
17
00020000
131072
Internal Fault
10 V low
18
00040000
262144
Brake Overload
Brake Overload
19
00080000
524288
U phase Loss
Brake Resistor
20
00100000
1048576
V phase Loss
Brake IGBT
21
00200000
2097152
W phase Loss
Speed Limit
Warnings and Alarms
Instruction Manual
MG11F522
Danfoss A/S © 08/2014 All rights reserved.
125
8
8