Input resistance, R
i
approx. 10 k
Ω
Maximum voltage
±
20 V
Current mode
switch S201/S202=On (I)
Current level
0/4-20 mA (scaleable)
Input resistance, R
i
approx. 200
Ω
Maximum current
30 mA
Resolution for analog inputs
10 bit (+ sign)
Accuracy of analog inputs
maximum error 0.5% of full scale
Bandwidth
200 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Mains
Functional
isolation
PELV isolation
Motor
DC-Bus
High
voltage
Control
+24V
RS485
18
37
130BA117.10
Figure 7.1 PELV Isolation of Analog Inputs
Pulse inputs
Programmable pulse inputs
2
Terminal number pulse
29, 33
Maximum frequency at terminal 29, 33
110 kHz (push-pull driven)
Maximum frequency at terminal 29, 33
5 kHz (open collector)
Minimum frequency at terminal 29, 33
4 Hz
Voltage level
see
Digital inputs
Maximum voltage on input
28 V DC
Input resistance, R
i
approx. 4 k
Ω
Pulse input accuracy (0.1–1 kHz)
maximum error 0.1% of full scale
Analog output
Number of programmable analog outputs
1
Terminal number
42
Current range at analog output
0/4–20 mA
Maximum resistor load to common at analog output
500
Ω
Accuracy on analog output
maximum error 0.8% of full scale
Resolution on analog output
8 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, RS-485 serial communication
Terminal number
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Terminal number 61
Common for terminals 68 and 69
The RS-485 serial communication circuit is functionally seated from other central circuits and galvanically isolated from the
supply voltage (PELV).
Digital output
Programmable digital/pulse outputs
2
Terminal number
27, 29
1)
Voltage level at digital/frequency output
0–24 V
Maximum output current (sink or source)
40 mA
General Specifications
Instruction Manual
MG11F522
Danfoss A/S © 08/2014 All rights reserved.