No.
Text
0
Serial port cannot be initialized. Contact the
Danfoss supplier or Danfoss Service.
256–258
Power EEPROM data is defective or too old.
512
Control board EEPROM data is defective or too old.
513
Communication timeout reading EEPROM data.
514
Communication timeout reading EEPROM data.
515
Application-oriented control cannot recognize the
EEPROM data.
516
Cannot write to the EEPROM because a write
command is in progress.
517
Write command is under timeout.
518
Failure in the EEPROM.
519
Missing or invalid barcode data in EEPROM.
783
Parameter value outside of min/max limits.
1024–1279 Sending a CAN message failed.
1281
Digital signal processor flash timeout.
1282
Power micro software version mismatch.
1283
Power EEPROM data version mismatch.
1284
Cannot read digital signal processor software
version.
1299
Option SW in slot A is too old.
1300
Option SW in slot B is too old.
1301
Option SW in slot C0 is too old.
1302
Option SW in slot C1 is too old.
1315
Option SW in slot A is not supported (not
allowed).
1316
Option SW in slot B is not supported (not allowed).
1317
Option SW in slot C0 is not supported (not
allowed).
1318
Option SW in slot C1 is not supported (not
allowed).
1379
Option A did not respond when calculating
platform version.
1380
Option B did not respond when calculating
platform version.
1381
Option C0 did not respond when calculating
platform version.
1382
Option C1 did not respond when calculating
platform version.
1536
An exception in the application-oriented control is
registered. Debug information written in LCP.
1792
DSP watchdog is active. Debugging of power part
data, motor-oriented control data not transferred
correctly.
2049
Power data restarted.
2064–2072 H081x: option in slot x has restarted.
2080–2088 H082x: option in slot x has issued a power-up wait.
2096–2104 H983x: option in slot x has issued a legal power-up
wait.
2304
Could not read any data from power EEPROM.
2305
Missing SW version from power unit.
No.
Text
2314
Missing power unit data from power unit.
2315
Missing SW version from power unit.
2316
Missing lo_statepage from power unit.
2324
Power card configuration is determined to be
incorrect at power-up.
2325
A power card has stopped communicating while
line power is applied.
2326
Power card configuration is determined to be
incorrect after the delay for power cards to
register.
2327
Too many power card locations have been
registered as present.
2330
Power size information between the power cards
does not match.
2561
No communication from DSP to ATACD.
2562
No communication from ATACD to DSP (state
running).
2816
Stack overflow control board module.
2817
Scheduler slow tasks.
2818
Fast tasks.
2819
Parameter thread.
2820
LCP stack overflow.
2821
Serial port overflow.
2822
USB port overflow.
2836
cfListMempool too small.
3072–5122 Parameter value is outside its limits.
5123
Option in slot A: Hardware incompatible with
control board hardware.
5124
Option in slot B: Hardware incompatible with
control board hardware.
5125
Option in slot C0: Hardware incompatible with
control board hardware.
5126
Option in slot C1: Hardware incompatible with
control board hardware.
5376–6231 Out of memory.
Table 8.4 Code Numbers for Internal Faults
ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gate drive card, or the ribbon cable between the
power card and gate drive card.
WARNING 40, Overload of digital output terminal 27
Check the load connected to terminal 27 or remove the
short-circuit connection. Check
parameter 5-00 Digital I/O
Mode
and
parameter 5-01 Terminal 27 Mode
.
Warnings and Alarms
VLT
®
HVAC Drive FC 102
130
Danfoss A/S © 08/2014 All rights reserved.
MG11F522