Size/type
Bussmann PN*
Rating
Siba
P500
170M8611
1100 A, 1000 V
20 781 32.1000
P560
170M8611
1100 A, 1000 V
20 781 32.1000
P630
170M6467
1400 A, 700 V
20 681 32.1400
P710
170M6467
1400 A, 700 V
20 681 32.1400
P800
170M8611
1100 A, 1000 V
20 781 32.1000
P1M0
170M6467
1400 A, 700 V
20 681 32.1400
Table 4.14 Enclosure Type F, Inverter Module DC Link Fuses, 380–480 V
*170M fuses from Bussmann shown use the -/80 visual indicator; -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and
amperage may be substituted for external use.
**Any minimum 500 V UL listed fuse with associated current rating may be used to meet UL requirements.
525–690 V, Enclosure types E and F
Size/type
Bussmann PN*
Rating
Ferraz
Siba
P450
170M4017
700 A, 700 V
6.9URD31D08A0700
20 610 32.700
P500
170M4017
700 A, 700 V
6.9URD31D08A0700
20 610 32.700
P560
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
P630
170M6013
900 A, 700 V
6.9URD33D08A0900
20 630 32.900
Table 4.15 Enclosure Type E, 525–690 V
Size/type
Bussmann PN*
Rating
Siba
Internal Bussmann
option
P710
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P800
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P900
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P1M0
170M7081
1600 A, 700 V
20 695 32.1600
170M7082
P1M2
170M7082
2000 A, 700 V
20 695 32.2000
170M7082
P1M4
170M7083
2500 A, 700 V
20 695 32.2500
170M7083
Table 4.16 Enclosure Type Size F, Electrical Fuses, 525–690 V
Size/type
Bussmann PN*
Rating
Siba
P710
170M8611
1100 A, 1000 V
20 781 32. 1000
P800
170M8611
1100 A, 1000 V
20 781 32. 1000
P900
170M8611
1100 A, 1000 V
20 781 32. 1000
P1M0
170M8611
1100 A, 1000 V
20 781 32. 1000
P1M2
170M8611
1100 A, 1000 V
20 781 32. 1000
P1M4
170M8611
1100 A, 1000 V
20 781 32.1000
Table 4.17 Enclosure Type F, Inverter Module DC Link Fuses, 525–690 V
*170M fuses from Bussmann shown use the -/80 visual indicator; -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and
amperage may be substituted for external use.
Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical A, 500/600/690 V maximum when
protected by the above fuses.
Supplementary fuses
Enclosure size
Bussmann PN*
Rating
E and F
KTK-4
4 A, 600 V
Table 4.18 SMPS Fuse
Electrical Installation
VLT
®
HVAC Drive FC 102
52
Danfoss A/S © 08/2014 All rights reserved.
MG11F522
4
4
Содержание VLT HVAC Drive FC 102
Страница 2: ......