0-01 Language
Option:
Function:
[10] Chinese
Part of language package 2
[20] Suomi
Part of language package 1
[22] English US
Part of language package 4
[27] Greek
Part of language package 4
[28] Bras.port
Part of language package 4
[36] Slovenian
Part of language package 3
[39] Korean
Part of language package 2
[40] Japanese
Part of language package 2
[41] Turkish
Part of language package 4
[42] Trad.Chinese
Part of language package 2
[43] Bulgarian
Part of language package 3
[44] Srpski
Part of language package 3
[45] Romanian
Part of language package 3
[46] Magyar
Part of language package 3
[47] Czech
Part of language package 3
[48] Polski
Part of language package 4
[49] Russian
Part of language package 3
[50] Thai
Part of language package 2
[51] Bahasa
Indonesia
Part of language package 2
[52] Hrvatski
Part of language package 3
NOTICE!
Parameter 1-20 Motor Power [kW]
,
,
and
parameter 1-23 Motor Frequency
will not have effect
when
parameter 1-10 Motor Construction
= [1] PM, non-
salient SPM.
1-20 Motor Power [kW]
Range:
Function:
Size
related
*
[ 0.09 -
3000.00
kW]
Enter the nominal motor power in kW
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
Depending on the choices made in
parameter 0-03 Regional Settings
, either
parameter 1-20 Motor Power [kW]
or
parameter 1-21 Motor Power [HP]
is made
invisible.
1-20 Motor Power [kW]
Range:
Function:
NOTICE!
This parameter cannot be adjusted
while the motor is running.
1-21 Motor Power [HP]
Range:
Function:
Size
related
*
[ 0.09 -
3000.00
hp]
Enter the nominal motor power in HP
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
Depending on the choices made in
parameter 0-03 Regional Settings
, either
parameter 1-20 Motor Power [kW]
or
parameter 1-21 Motor Power [HP]
is made
invisible.
NOTICE!
This parameter cannot be adjusted
while the motor is running.
1-22 Motor Voltage
Range:
Function:
Size
related
*
[ 10 -
1000 V]
Enter the nominal motor voltage
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
NOTICE!
This parameter cannot be adjusted
while the motor is running.
1-23 Motor Frequency
Range:
Function:
Size
related
*
[20 -
1000
Hz]
Select the motor frequency value from the
motor nameplate data. For 87 Hz operation
with 230/400 V motors, set the nameplate
data for 230 V/50 Hz. Adapt
parameter 4-13 Motor Speed High Limit [RPM]
and
parameter 3-03 Maximum Reference
to
the 87 Hz application.
NOTICE!
This parameter cannot be adjusted while the motor is
running.
How to Program
VLT
®
HVAC Drive FC 102
80
Danfoss A/S © 08/2014 All rights reserved.
MG11F522
6