Minimum ambient temperature at reduced performance
-10
°
C (14 °F)
Temperature during storage/transport
-25 to +65/70
°
C (-13 °F to + 149/158 °F)
Maximum altitude above sea level without derating
1000 m (3300 ft)
Maximum altitude above sea level with derating
3000 m (10,000 ft)
For more information on derating for high altitude, see the section on special conditions in the design guide.
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Energy efficiency class
2)
IE2
For more information, see the section on special conditions in the design guide.
2) Determined according to EN50598-2 at:
•
Rated load
•
90% rated frequency
•
Switching frequency factory setting
•
Switching pattern factory setting
7.3 Cable Specifications
Cable lengths and cross-sections
Maximum motor cable length, shielded/armored
150 m (500 ft)
Maximum motor cable length, non-shielded/unarmored
300 m (1000 ft)
Maximum cross-section to motor, line power, load sharing and brake
1)
Maximum cross-section to control terminals, rigid wire
1.5 mm
2
/16 AWG (2 x 0.75 mm
2
)
Maximum cross-section to control terminals, flexible cable
1 mm
2
/18 AWG
Maximum cross-section to control terminals, cable with enclosed core
0.5 mm
2
/20 AWG
Minimum cross-section to control terminals
0.25 mm
2
(AWG 3/4)
1) See chapter 7.5 Electrical Data for more information.
7.4 Control Input/Ouput and Control Data
Digital inputs
Programmable digital inputs
4 (6)
Terminal number
18, 19, 27
1)
, 29
1)
, 32, 33,
Logic
PNP or NPN
Voltage level
0–24 V DC
Voltage level, logic'0' PNP
<
5 V DC
Voltage level, logic'1' PNP
>
10 V DC
Voltage level, logic '0' NPN
>
19 V DC
Voltage level, logic '1' NPN
<
14 V DC
Maximum voltage on input
28 V DC
Input resistance, R
i
approx. 4 k
Ω
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
Analog inputs
Number of analog inputs
2
Terminal number
53, 54
Modes
voltage or current
Mode select
switches S201 and S202
Voltage mode
switch S201/S202 = OFF (U)
Voltage level
0–10 V (scaleable)
General Specifications
VLT
®
HVAC Drive FC 102
114
Danfoss A/S © 08/2014 All rights reserved.
MG11F522
7