7.5 Electrical Data
Line Power Supply 3 x 380–480 V AC
P315
P355
P400
P450
Typical shaft output at 400 V [kW]
315
355
400
450
Typical shaft output at 460 V [hp]
450
500
600
600
Enclosure protection rating IP21
E1
E1
E1
E1
Enclosure protection rating IP54
E1
E1
E1
E1
Enclosure protection rating IP00
E2
E2
E2
E2
Output current
Continuous (at 400 V) [A]
600
658
745
800
Intermittent (60 s overload) (at 400 V)
[A]
660
724
820
880
Continuous (at 460/480 V) [A]
540
590
678
730
Intermittent (60 s overload) (at
460/480 V) [A]
594
649
746
803
Continuous KVA (at 400 V) [KVA]
416
456
516
554
Continuous KVA (at 460 V) [KVA]
430
470
540
582
Maximum input current
Continuous (at 400 V) [A]
590
647
733
787
Continuous (at 460/480 V) [A]
531
580
667
718
Maximum cable size, line power,
motor and load share [mm
2
(AWG
2)
)]
4 x 240
(4 x 500 mcm)
4 x 240
(4 x 500 mcm)
4 x 240
(4 x 500 mcm)
4 x 240
(4 x 500 mcm)
Maximum cable size, brake [mm
2
(AWG
2)
)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Maximum external pre-fuses [A]
1)
700
800
900
900
Estimated power loss
at rated max. load [W]
3)
, 400 V
6790
7701
8677
9473
Estimated power loss
at rated maximum load [W]
3)
, 460 V
6082
6953
7819
8527
Weight,
enclosure protection rating IP21, IP54
[kg (lb)]
263 (580)
270 (595.5)
272 (600)
313 (690)
Weight,
enclosure protection rating IP00 [kg
(lb)]
221 (487.3)
234 (516)
236 (520.3)
277 (611)
Efficiency
4)
0.98
Output frequency
0–590 Hz
Heatsink overtemperature trip
110
°
C (230 °F)
Power card ambient trip
75
°
C (167 °F)
85
°
C (185 °F)
Table 7.1 Line Power Supply 3 x 380–480 V AC
General Specifications
VLT
®
HVAC Drive FC 102
118
Danfoss A/S © 08/2014 All rights reserved.
MG11F522
7
7