Control card, 10 V DC output
A)
Terminal number
50
Output voltage
10.5 V
±
0.5 V
Max. load
25 mA
A)
All inputs, outputs, circuits, DC supplies and relay contacts are galvanically isolated from the supply voltage (PELV) and
other high-voltage terminals.
Surroundings
Enclosure
IP20
Enclosure kit available
IP21, TYPE 1
Vibration test
1.0 g
Max. relative humidity
5%-95% (IEC 60721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60721-3-3), coated (standard) frame H1-H5
Class 3C3
Aggressive environment (IEC 60721-3-3), non-coated frame H6-H10
Class 3C2
Aggressive environment (IEC 60721-3-3), coated (optional) frame H6-H10
Class 3C3
Aggressive environment (IEC 60721-3-3), non-coated frame I2-I8
Class 3C2
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
See max. output current at 40/50
°
C in
8.1.2 Mains Supply 3x380-480 V AC
Derating for high ambient temperature, see
8.5 Derating according to Ambient Temperature and Switching
Frequency8.5 Derating according to Ambient Temperature and Switching Frequency
Minimum ambient temperature during full-scale operation
0
°
C
Minimum ambient temperature at reduced performance
-20
°
C
Minimum ambient temperature at reduced performance
-10
°
C
Temperature during storage/transport
-30 to +65/70
°
C
Maximum altitude above sea level without derating
1000 m
Maximum altitude above sea level with derating
3000 m
Derating for high altitude, see
Safety standards
EN/IEC 61800-5-1, UL 508C
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-3-12, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN
61000-4-5, EN 61000-4-6
General Specifications and ...
VLT
®
HVAC Basic Drive FC 101 Design Guide
108
MG18C502 - Rev. 2013-09-06