Cable length [m]
AC line voltage [V]
Rise time [usec]
V
peak
[kV]
dU/dt [kV/usec]
600 V 7.5 kW
5
525
0,192
0,972
4,083
50
525
0,356
1,32
2,949
5
600
0,184
1,06
4,609
50
600
0,42
1,49
2,976
Table 8.10
8.5 Derating according to Ambient
Temperature and Switching Frequency
The ambient temperature measured over 24 hours should
be at least 5
o
C lower than the max. ambient temperature.
If the frequency converter is operated at high ambient
temperature, the continuous output current should be
decreased.
110%
100%
90 %
80 %
70 %
60 %
50 %
40 %
30 %
20 %
10 %
0
I
out
[%]
0
2
5
10
16
40
o
C
50
o
C
45
o
C
fsw[kHz]
130BC217.10
Illustration 8.1 200 V IP20 H1 0.25-0.75 kW
f
sw
[kHz]
2
0
10
0
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
110%
I
out
[%]
16
40
45
50
5
o
C
o
C
o
C
130BC218.10
Illustration 8.2 400 V IP20 H1 0.37-1.5 kW
f
sw
[kHz]
2
0
10
0
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
110%
I
out
[%]
16
40
45
50
5
o
C
o
C
o
C
130BC219.10
Illustration 8.3 200 V IP20 H2 2.2 kW
f
sw
[kHz]
2
0
10
0
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
110%
I
out
[%]
16
40
45
50
5
o
C
o
C
o
C
130BC220.10
Illustration 8.4 400 V IP20 H2 2.2-4.0 kW
f
sw
[kHz]
2
0
10
0
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
110%
I
out
[%]
16
40
45
50
5
o
C
o
C
o
C
130BC221.10
Illustration 8.5 200 V IP20 H3 3.7 kW
General Specifications and ...
VLT
®
HVAC Basic Drive FC 101 Design Guide
112
MG18C502 - Rev. 2013-09-06
8
8
Содержание VLT HVAC Basic Drive FC 101
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT HVAC Basic Drive FC 101 www danfoss com drives...
Страница 2: ......
Страница 123: ...Index VLT HVAC Basic Drive FC 101 Design Guide MG18C502 Rev 2013 09 06 121...
Страница 124: ...www danfoss com drives MG18C502 130R0222 MG18C502 Rev 2013 09 05...