Frame
IP class
Power
Height
[mm] A
Width
[mm] B
Depth [mm]
C
IP21 kit
ordering
no.
Type 1 kit
ordering no.
3 x 200-240 V 3 x 380-480 V 3 x 525-600 V
H1
IP20
0.25-1.5 kW
0.37-1.5 kW
293
81
173
132B0212
132B0222
H2
IP20
2.2 kW
2.2-4 kW
322
96
195
132B0213
132B0223
H3
IP20
3.7 kW
5.5-7.5 kW
346
106
210
132B0214
132B0224
H4
IP20
5.5-7,5 kW
11-15 kW
374
141
245
132B0215
132B0225
H5
IP20
11 kW
18.5-22 kW
418
161
260
132B0216
132B0226
H6
IP20
15-18.5 kW
30-45 kW
18.5-30 kW
663
260
242
132B0217
132B0217
H7
IP20
22-30 kW
55-75 kW
37-55 kW
807
329
335
132B0218
132B0218
H8
IP20
37-45 kW
90 kW
75-90 kW
943
390
335
132B0219
132B0219
H9
IP20
2.2-7.5 kW
372
130
205
132B0220
132B0220
H10
IP20
11-15 kW
475
165
249
132B0221
132B0221
Table 3.3 Enclosure Kit Specifications
3.1.4 Decoupling Plate
Use the decoupling plate for EMC correct installation.
Shown here on a H3 enclosure.
130BB793.10
99
99
Illustration 3.7 Decoupling Plate
Power [kW]
Decoupling plate
Frame
IP class
3 x 200-240 V
3 x 380-480 V
3 x 525-600 V
H1
IP20
0.25-1.5
0.37-1.5
132B0202
H2
IP20
2.2
2.2-4
132B0202
H3
IP20
3.7
5.5-7.5
132B0204
H4
IP20
5.5-7.5
11-15
132B0205
H5
IP20
11
18.5-22
130B0205
H6
IP20
15-18.5
30
18.5-30
132B0207
H6
IP20
37-45
132B0242
H7
IP20
22-30
55
37-55
132B0208
H7
IP20
75
132B0243
H8
IP20
37-45
90
75-90
132B0209
Table 3.4 Decoupling Plate Specifications
NOTICE
For H9 and H10 frequency converters, the decoupling plates are included in the accessory bag.
Selection
VLT
®
HVAC Basic Drive FC 101 Design Guide
MG18C502 - Rev. 2013-09-06
43
3
3
Содержание VLT HVAC Basic Drive FC 101
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT HVAC Basic Drive FC 101 www danfoss com drives...
Страница 2: ......
Страница 123: ...Index VLT HVAC Basic Drive FC 101 Design Guide MG18C502 Rev 2013 09 06 121...
Страница 124: ...www danfoss com drives MG18C502 130R0222 MG18C502 Rev 2013 09 05...