Cable length [m]
AC line voltage [V]
Rise time [usec]
V
peak
[kV]
dU/dt [kV/usec]
400 V 11 kW
5
400
0,116
0,69
4871
25
400
0,204
0,985
3799
50
400
0,316
1,01
2563
400 V 15 kW
5
400
0,139
0,864
4,955
50
400
0,338
1,008
2,365
400 V 18.5 kW
5
400
0,132
0,88
5.220
25
400
0,172
1.026
4.772
50
400
0,222
1,00
3.603
400 V 22 kW
5
400
0,132
0,88
5.220
25
400
0,172
1.026
4.772
50
400
0,222
1,00
3.603
400 V 30 kW
10
400
0,376
0,92
1,957
50
400
0,536
0,97
1,448
100
400
0,696
0,95
1,092
150
400
0,8
0,965
0,965
10
480
0,384
1,2
2,5
50
480
0,632
1,18
1,494
100
480
0,712
1,2
1,348
150
480
0,832
1,17
1,125
10
500
0,408
1,24
2,431
50
500
0,592
1,29
1,743
100
500
0,656
1,28
1,561
150
500
0,84
1,26
1,2
400 V 37 kW
10
400
0,276
0,928
2,69
50
400
0,432
1,02
1,889
10
480
0,272
1,17
3,441
50
480
0,384
1,21
2,521
10
500
0,288
1,2
3,333
50
500
0,384
1,27
2,646
400 V 45 kW
10
400
0,3
0,936
2,496
50
400
0,44
0,924
1,68
100
400
0,56
0,92
1,314
150
400
0,8
0,92
0,92
10
480
0,3
1,19
3,173
50
480
0,4
1,15
2,3
100
480
0,48
1,14
1,9
150
480
0,72
1,14
1,267
10
500
0,3
1,22
3,253
50
500
0,38
1,2
2,526
100
500
0,56
1,16
1,657
150
500
0,74
1,16
1,254
400 V 55 kW
10
400
0,46
1,12
1,948
480
0,468
1,3
2,222
400 V 75 kW
10
400
0,502
1,048
1,673
480
0,52
1,212
1,869
500
0,51
1,272
1,992
400 V 90 kW
10
400
0,402
1,108
2,155
400
0,408
1,288
2,529
400
0,424
1,368
2,585
General Specifications and ...
VLT
®
HVAC Basic Drive FC 101 Design Guide
MG18C502 - Rev. 2013-09-06
111
8
8
Содержание VLT HVAC Basic Drive FC 101
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT HVAC Basic Drive FC 101 www danfoss com drives...
Страница 2: ......
Страница 123: ...Index VLT HVAC Basic Drive FC 101 Design Guide MG18C502 Rev 2013 09 06 121...
Страница 124: ...www danfoss com drives MG18C502 130R0222 MG18C502 Rev 2013 09 05...