Digital input 29 as thermistor input
Fault: >2.9 k
Ω
and no fault: <800
Ω
Digital input 29 as Pulse input
Max frequency 32 kHz Push-Pull-Driven & 5 kHz (O.C.)
Analog inputs
Number of analog inputs
2
Terminal number
53, 54
Terminal 53 mode
Parameter 6-19: 1=voltage, 0=current
Terminal 54 mode
Parameter 6-29: 1=voltage, 0=current
Voltage level
0-10 V
Input resistance, R
i
approx. 10 k
Ω
Max. voltage
20 V
Current level
0/4 to 20 mA (scalable)
Input resistance, R
i
<500
Ω
Max. current
29 mA
Analog output
Number of programmable analog outputs
2
Terminal number
42, 45
1)
Current range at analog output
0/4-20 mA
Max. load to common at analog output
500
Ω
Max. voltage at analog output
17 V
Accuracy on analog output
Max. error: 0.4% of full scale
Resolution on analog output
10 bit
1)
Terminal 42 and 45 can also be programmed as digital outputs.
Digital output
Number of digital outputs
2
Terminal number
42, 45
1)
Voltage level at digital output
17 V
Max. output current at digital output
20 mA
Max. load at digital output
1 k
Ω
1) Terminals 42 and 45 can also be programmed as analog output.
Control card, RS-485 serial communication
A)
Terminal number
68 (P, TX+, RX+), 69 (N, TX-, RX-)
Terminal number
61 Common for terminals 68 and 69
Control card, 24 V DC output
Terminal number
12
Max. load
80 mA
Relay output
Programmable relay output
2
Relay 01 and 02
01-03 (NC), 01-02 (NO), 04-06 (NC), 04-05 (NO)
Max. terminal load (AC-1)
1)
on 01-02/04-05 (NO) (Resistive load)
250 V AC, 3 A
Max. terminal load (AC-15)
1)
on 01-02/04-05 (NO) (Inductive load @ cos
φ
0.4)
250 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 01-02/04-05 (NO) (Resistive load)
30 V DC, 2 A
Max. terminal load (DC-13)
1)
on 01-02/04-05 (NO) (Inductive load)
24 V DC, 0.1 A
Max. terminal load (AC-1)
1)
on 01-03/04-06 (NC) (Resistive load)
250 V AC, 3 A
Max. terminal load (AC-15)
1)
on 01-03/04-06 (NC) (Inductive load @ cos
φ
0.4)
250 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 01-03/04-06
(NC) (Resistive load)
30 V DC, 2 A
Min. terminal load on 01-03 (NC), 01-02 (NO) 24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
1)
IEC 60947 parts 4 and 5.
General Specifications and ...
VLT
®
HVAC Basic Drive FC 101 Design Guide
MG18C502 - Rev. 2013-09-06
107
8
8
Содержание VLT HVAC Basic Drive FC 101
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT HVAC Basic Drive FC 101 www danfoss com drives...
Страница 2: ......
Страница 123: ...Index VLT HVAC Basic Drive FC 101 Design Guide MG18C502 Rev 2013 09 06 121...
Страница 124: ...www danfoss com drives MG18C502 130R0222 MG18C502 Rev 2013 09 05...