Parameter
Range
Default
Function
1-73 Flying Start
[0] Disabled
[1] Enabled
0
Select
[1] Enable
to enable the frequency
converter to catch a spinning motor. I.e. fan
applications. When PM is selected, Flying Start
is enabled.
3-02 Minimum Reference
-4999-4999
0
The minimum reference is the lowest value
obtainable by summing all references
3-03 Maximum Reference
-4999-4999
50
The maximum reference is the highest value
obtainable by summing all references
3-10 Preset Reference
-100-100%
0
Enter the set point
3-41 Ramp 1 Ramp Up Time
0.05-3600.0 s
Size related
Ramp up time from 0 to rated
1-23 Motor
Frequency
if Asynchron motor is selected;
ramp up time from 0 to 1-25 Motor Nominal
Speed if PM motor is selected"
3-42 Ramp 1 Ramp Down Time
0.05-3600.0 s
Size related
Ramp down time from rated
1-23 Motor
Frequency
to 0 if Asynchron motor is selected;
ramp down time from
1-25 Motor Nominal
Speed
to 0 if PM motor is selected
4-12 Motor Speed Low Limit [Hz]
0.0-400 Hz
0.0 Hz
Enter the minimum limit for low speed
4-14 Motor Speed High Limit [Hz]
0-400 Hz
65 Hz
Enter the minimum limit for high speed
4-19 Max Output Frequency
0-400
Size related
Enter the maximum output frequency value
6-20 Terminal 54 Low Voltage
0-10 V
0.07 V
Enter the voltage that corresponds to the low
reference value
6-21 Terminal 54 High Voltage
0-10 V
10 V
Enter the voltage that corresponds to the low
high reference value
6-22 Terminal 54 Low Current
0-20 mA
4
Enter the current that corresponds to the high
reference value
6-23 Terminal 54 High Current
0-20 mA
20
Enter the current that corresponds to the high
reference value
6-24 Terminal 54 Low Ref./Feedb.
Value
-4999-4999
0
Enter the feedback value that corresponds to
the voltage or current set in
6-20 Terminal 54
Low Voltage
/
6-22 Terminal 54 Low Current
6-25 Terminal 54 High Ref./Feedb.
Value
-4999-4999
50
Enter the feedback value that corresponds to
the voltage or current set in
6-21 Terminal 54
High Voltage
/
6-23 Terminal 54 High Current
6-26 Terminal 54 Filter Time
Constant
0-10 s
0.01
Enter the filter time comstant
6-29 Terminal 54 mode
[0] Current
[1] Voltage
1
Select if terminal 54 is used for current- or
voltage input
20-81 PI Normal/ Inverse Control
[0] Normal
[1] Inverse
0
Select
[0] Normal
to set the process control to
increase the output speed when the process
error is positive. Select
[1] Inverse
to reduce
the output speed.
20-83 PI Start Speed [Hz]
0-200 Hz
0
Enter the motor speed to be attained as a
start signal for commencement of PI control
20-93 PI Proportional Gain
0-10
0.01
Enter the process controller proportional gain.
Quick control is obtained at high amplifi-
cation. However if amplification is too great,
the process may become unstable
20-94 PI Integral Time
0.1-999.0 s
999.0 s
Enter the process controller integral time.
Obtain quick control through a short integral
time, though if the integral time is too short,
the process becomes unstable. An excessively
long integral time disables the integral action.
Table 2.8 Closed Loop Set-up Wizard
Product Overview
VLT
®
HVAC Basic Drive FC 101 Design Guide
30
MG18C502 - Rev. 2013-09-06
2
2
Содержание VLT HVAC Basic Drive FC 101
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT HVAC Basic Drive FC 101 www danfoss com drives...
Страница 2: ......
Страница 123: ...Index VLT HVAC Basic Drive FC 101 Design Guide MG18C502 Rev 2013 09 06 121...
Страница 124: ...www danfoss com drives MG18C502 130R0222 MG18C502 Rev 2013 09 05...