
Circuit Breaker
Fuse
UL
Non UL
UL
Non UL
Bussmann
Bussmann
Bussmann
Bussmann
Max fuse
Power [kW]
Type RK5
Type RK1
Type J
Type T
Type G
3x380-480 V IP54
0.75
PKZM0-16
FRS-R-10
KTS-R-10
JKS-10
JJS-10
16
1.5
PKZM0-16
FRS-R-10
KTS-R-10
JKS-10
JJS-10
16
2.2
PKZM0-16
FRS-R-15
KTS-R-15
JKS-15
JJS-15
16
3
PKZM0-16
FRS-R-15
KTS-R-15
JKS-15
JJS-15
16
4
PKZM0-16
FRS-R-15
KTS-R-15
JKS-15
JJS-15
16
5.5
PKZM0-25
FRS-R-25
KTS-R-25
JKS-25
JJS-25
25
7.5
PKZM0-25
FRS-R-25
KTS-R-25
JKS-25
JJS-25
25
11
PKZM4-63
FRS-R-50
KTS-R-50
JKS-50
JJS-50
63
15
PKZM4-63
FRS-R-50
KTS-R-50
JKS-50
JJS-50
63
18.5
PKZM4-63
FRS-R-80
KTS-R-80
JKS-80
JJS-80
63
22
Moeller NZMB1-A125
FRS-R-80
KTS-R-80
JKS-80
JJS-80
125
30
FRS-R-125
KTS-R-125
JKS-125
JJS-125
125
37
FRS-R-125
KTS-R-125
JKS-125
JJS-125
125
45
Moeller NZMB2-A160
FRS-R-125
KTS-R-125
JKS-125
JJS-125
160
55
FRS-R-200
KTS-R-200
JKS-200
JJS-200
160
75
Moeller NZMB2-A250
FRS-R-200
KTS-R-200
JKS-200
JJS-200
200
90
FRS-R-250
KTS-R-250
JKS-200
JJS-200
200
Table 5.17 Circuit Breakers and Fuses
How to Install
VLT
®
HVAC Basic Drive FC 101 Design Guide
64
MG18C502 - Rev. 2013-09-06
5
5
Содержание VLT HVAC Basic Drive FC 101
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT HVAC Basic Drive FC 101 www danfoss com drives...
Страница 2: ......
Страница 123: ...Index VLT HVAC Basic Drive FC 101 Design Guide MG18C502 Rev 2013 09 06 121...
Страница 124: ...www danfoss com drives MG18C502 130R0222 MG18C502 Rev 2013 09 05...