8.2 General Specifications
Protection and features
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the heat sink ensures that the frequency converter trips in case of overtemperature
•
The frequency converter is protected against short-circuits between motor terminals U, V, W.
•
When a motor phase is missing, the frequency converter trips and issues an alarm.
•
When a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
•
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips, when the intermediate
circuit voltage is too low or too high.
•
The frequency converter is protected against earth faults on motor terminals U, V, W.
Mains supply (L1, L2, L3)
Supply voltage
200-240 V
±
10%
Supply voltage
380-480 V
±
10%
Supply voltage
525-600 V
±
10%
Supply frequency
50/60 Hz
Max. imbalance temporary between mains phases
3.0% of rated supply voltage
True Power Factor (
λ
)
≥
0.9 nominal at rated load
Displacement Power Factor (cos
φ
) near unity
(>0.98)
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H1-H5, I2, I3, I4
Max. 2 times/min.
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H6-H8, I6-I8
Max. 1 time/min.
Environment according to EN 60664-1
overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/480 V
maximum.
Motor output (U, V, W)
Output voltage
0-100% of supply voltage
Output frequency
0-200 Hz (VVC
plus
), 0-400 Hz (u/f)
Switching on output
Unlimited
Ramp times
0.05-3600 s
Cable lengths and cross sections
Max. motor cable length, screened/armoured (EMC correct installation)
See
Max. motor cable length, unscreened/unarmoured
50 m
Max. cross section to motor, mains*
Cross section DC terminals for filter feedback on enclosure frame H1-H3, I2, I3, I4
4 mm
2
/11 AWG
Cross section DC terminals for filter feedback on enclosure frame H4-H5
16 mm
2
/6 AWG
Maximum cross section to control terminals, rigid wire
2.5 mm
2
/14 AWG)
Maximum cross section to control terminals, flexible cable
2.5 mm
2
/14 AWG)
Minimum cross section to control terminals
0.05 mm
2
/30 AWG
*See
8.1.2 Mains Supply 3x380-480 V AC
for more information
Digital inputs
Programmable digital inputs
4
Terminal number
18, 19, 27, 29
Logic
PNP or NPN
Voltage level
0-24 V DC
Voltage level, logic '0' PNP
<5 V DC
Voltage level, logic '1' PNP
>10 V DC
Voltage level, logic '0' NPN
>19 V DC
Voltage level, logic '1' NPN
<14 V DC
Maximum voltage on input
28 V DC
Input resistance, R
i
Approx. 4 k
Ω
General Specifications and ...
VLT
®
HVAC Basic Drive FC 101 Design Guide
106
MG18C502 - Rev. 2013-09-06
8
8