5.2.3 Fuses and Circuit Breakers
Branch circuit protection
To protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc.,
must be short-circuit and overcurrent protected according to national and local regulations.
Short circuit protection
Danfoss recommends using the fuses and circuit breakers listed in
to protect service personnel or other
equipment in case of an internal failure in the unit or short-circuit on DC-link. The frequency converter provides full short
circuit protection in case of a short-circuit on the motor.
Overcurrent protection
Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection must always be
carried out according to local and national regulations. Circuit breakers and fuses must be designed for protection in a
circuit capable of supplying a maximum of 100,000 A
rms
(symmetrical), 480 V maximum.
UL/Non UL compliance
Use the circuit breakers or fuses listed in
, to ensure compliance with UL or IEC 61800-5-1.
Circuit breakers must be designed for protection in a circuit capable of supplying a maximum of 10,000 Arms (symmetrical),
480 V maximum.
NOTICE
In the event of malfunction, failure to follow the protection recommendation may result in damage to the frequency
converter.
Circuit Breaker
Fuse
UL
Non UL
UL
Non UL
Bussmann
Bussmann
Bussmann
Bussmann
Max fuse
Power [kW]
Type RK5
Type RK1
Type J
Type T
Type G
3x200-240 V IP20
0.25
FRS-R-10
KTN-R10
JKS-10
JJN-10
10
0.37
FRS-R-10
KTN-R10
JKS-10
JJN-10
10
0.75
FRS-R-10
KTN-R10
JKS-10
JJN-10
10
1.5
FRS-R-10
KTN-R10
JKS-10
JJN-10
10
2.2
FRS-R-15
KTN-R15
JKS-15
JJN-15
16
3.7
FRS-R-25
KTN-R25
JKS-25
JJN-25
25
5.5
FRS-R-50
KTN-R50
JKS-50
JJN-50
50
7.5
FRS-R-50
KTN-R50
JKS-50
JJN-50
50
11
FRS-R-80
KTN-R80
JKS-80
JJN-80
65
15
Cutler-Hammer
EGE3100FFG
Moeller NZMB1-
A125
FRS-R-100
KTN-R100
JKS-100
JJN-100
125
18.5
FRS-R-100
KTN-R100
JKS-100
JJN-100
125
22
Cutler-Hammer
JGE3150FFG
Moeller NZMB1-
A160
FRS-R-150
KTN-R150
JKS-150
JJN-150
160
30
FRS-R-150
KTN-R150
JKS-150
JJN-150
160
37
Cutler-Hammer
JGE3200FFG
Moeller NZMB1-
A200
FRS-R-200
KTN-R200
JKS-200
JJN-200
200
45
FRS-R-200
KTN-R200
JKS-200
JJN-200
200
Table 5.15 Circuit Breakers and Fuses
How to Install
VLT
®
HVAC Basic Drive FC 101 Design Guide
62
MG18C502 - Rev. 2013-09-06
5
5
Содержание VLT HVAC Basic Drive FC 101
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT HVAC Basic Drive FC 101 www danfoss com drives...
Страница 2: ......
Страница 123: ...Index VLT HVAC Basic Drive FC 101 Design Guide MG18C502 Rev 2013 09 06 121...
Страница 124: ...www danfoss com drives MG18C502 130R0222 MG18C502 Rev 2013 09 05...