Parameter
Range
Default
Function
6-11 Terminal 53 High
Voltage
0-10 V
10 V
Enter the voltage that corresponds to the high
reference value
6-12 Terminal 53 Low
Current
0-20 mA
4
Enter the current that corresponds to the low
reference value
6-13 Terminal 53 High
Current
0-20 mA
20
Enter the current that corresponds to the high
reference value
6-19 Terminal 53 mode
[0] Current
[1] Voltage
1
Select if terminal 53 is used for current- or voltage
input
Table 6.4 Open Loop Application
How to Programme
VLT
®
HVAC Basic Drive FC 101 Design Guide
MG18C502 - Rev. 2013-09-06