B
a
ck
OK
Com.
On
Warn.
Alarm
Hand
On
Off
Reset
Auto
On
Menu Status Quick
Menu
Main
Menu
L1
L2
L3
PE
Min. 16 mm
2
Equalizing cable
Control cables
All cable entries in
one side of panel
Earthing rail
Cable insula-
tion stripped
Output con-
tactor etc.
Motor cable
Motor, 3 phases and
PLC etc.
Panel
Mains-supply
Min. 200mm
between control
cable, mains cable
and between mains
motor cable
PLC
Protective earth
Reinforced protective earth
130BB761.11
Illustration 5.20 EMC-correct Electrical Installation
NOTICE
For North America use metal conduits instead of shielded cables.
How to Install
VLT
®
HVAC Basic Drive FC 101 Design Guide
66