Parameter
[Units]
[kW]
[HP]
*
[V]
[Hz]
[A]
[RPM]
[Hz]
[s]
[s]
[RPM]
* [Hz]
[RPM]
* [Hz]
Par. 3-19
Jog Speed [RPM]
[RPM]
*
[Hz]
**
Table 6.2: Quick Setup parameters
*The display showing depends on choices made in par. 0-02
Motor
Speed Unit
and par. 0-03
Regional Settings
. The default settings of
par. 0-02
Motor Speed Unit
and par. 0-03
Regional Settings
depend on
which region of the world the frequency converter is supplied to but
can be re-programmed as required.
** Par. 5-40
, is an array, where one may choose be-
tween Relay1 [0] or Relay2 [1]. Standard setting is Relay1 [0] with the
default choice Alarm [9].
See the parameter description in the section
Commonly Used Parame-
ters
.
For a detailed information about settings and programming, please see
the
VLT HVAC Drive Programming Guide, MG.11.CX.YY
x=version number
y=language
NB!
If [No Operation] is selected in par. 5-12
, no connection to +24V on terminal 27
is necessary to enable start.
If [Coast Inverse] (factory default value) is selected
in par. 5-12
, a connection
to +24V is necessary to enable start.
VLT HVAC Drive High Power Operating In-
structions
6 How to Programme
MG.11.F3.02 - VLT
®