Frame size
Bussmann PN*
Rating
Alternative
Fuses
F
LPJ-30 SP or
SPI
30 A, 600 V
Any listed Class
J Dual Ele-
ment, Time
Delay, 30 A
Table 4.13: 30 A Fuse Protected Terminal Fuse
Frame size
Bussmann PN*
Rating
Alternative
Fuses
F
LPJ-6 SP or
SPI
6 A, 600 V
Any listed Class
J Dual Ele-
ment, Time
Delay, 6 A
Table 4.14: Control Transformer Fuse
Frame size
Bussmann PN*
Rating
F
GMC-800MA
800 mA, 250 V
Table 4.15: NAMUR Fuse
Frame size
Bussmann PN*
Rating
Alternative
Fuses
F
LP-CC-6
6 A, 600 V
Any listed Class
CC, 6 A
Table 4.16: Safety Relay Coil Fuse with PILS Relay
VLT HVAC Drive High Power Operating In-
structions
4 Electrical Installation
MG.11.F3.02 - VLT
®
is a registered Danfoss trademark
69