4.3.2 Switches S201, S202, and S801
Switches S201 (A53) and S202 (A54) are used to select a current
(0-20mA) or a voltage (-10 to 10V) configuration of the analog input
terminals 53 and 54 respectively.
Switch S801 (BUS TER.) can be used to enable termination on the
RS-485 port (terminals 68 and 69).
See drawing
Diagram showing all electrical terminals
in section
Electri-
cal Installation.
Default setting:
S201 (A53) = OFF (voltage input)
S202 (A54) = OFF (voltage input)
S801 (Bus termination) = OFF
NB!
When changing the function of S201, S202 or S801
be careful not to use force for the switch over. It is
recommended to remove the LCP fixture (cradle)
when operating the switches. The switches must not
be operated with power on the frequency converter.
130B
T310.10
1
2
N O
VLT
BUS TER.
OFF-ON
A53 A54
U- I U- I
4.4 Final Set-up and Test
To test the set-up and ensure that the frequency converter is running,
follow these steps.
Step 1. Locate the motor name plate
NB!
The motor is either star- (Y) or delta- connected (Δ).
This information is located on the motor name plate
data.
THREE PHASE INDUCTION MOTOR
kW 400
MOD MCV 315E
Nr. 135189 12 04
PRIMARY
SECONDARY
V 690 A
V
A
V
A
V
A
410.6 CONN Y
CONN
CONN
CONN
ENCLOSURE
CAUTION
COS f
ALT
RISE
m
SF 1.15
0.85
AMB 40
1000
80
°C
°C
IP23
40
IL/IN 6.5
HP 536
mm 1481
Hz
DESIGN
50
N
DUTY
INSUL
WEIGHT 1.83 ton
EFFICIENCY % 95.8%
95.8% 75%
100%
S1
I
130BA767.10
Step 2. Enter the motor name plate data in this parameter list.
To access this list first press the [QUICK MENU] key then select “Q2
Quick Setup”.
VLT HVAC Drive High Power Operating In-
structions
4 Electrical Installation
MG.11.F3.02 - VLT
®
is a registered Danfoss trademark
79
4