[101]
Reference Min-Max
Minimum reference - Maximum reference, (0-20 mA)
[102]
Fe-200%
-200% to +200% of par. 20-14
Maximum Reference/Feedb.
, (0-20 mA)
[103]
Motor cur. 0-Imax
0 - Inverter Max. Current (par. 16-37
Inv. Max. Current
), (0-20 mA)
[104]
Torque 0-Tlim
0 - Torque limit (par. 4-16
Torque Limit Motor Mode
), (0-20 mA)
[105]
Torque 0-Tnom
0 - Motor rated torque, (0-20 mA)
[106]
Power 0-Pnom
0 - Motor rated power, (0-20 mA)
[107]
Speed 0-HighLim
0 - Speed High Limit (par. 4-13
and par. 4-14
), (0-20 mA)
[113]
Ext. Closed Loop 1
0 - 100%, (0-20 mA)
[114]
Ext. Closed Loop 2
0 - 100%, (0-20 mA)
[115]
Ext. Closed Loop 3
0 - 100%, (0-20 mA)
[130]
Out frq 0-100 4-20mA
0 - 100 Hz
[131]
Reference 4-20mA
Minimum Reference - Maximum Reference
[132]
Feedback 4-20mA
-200% to +200% of par. 20-14
Maximum Reference/Feedb.
[133]
Motor cur. 4-20mA
0 - Inverter Max. Current (par. 16-37
Inv. Max. Current
)
[134]
Torq.0-lim 4-20 mA
0 - Torque limit (par. 4-16
Torque Limit Motor Mode
)
[135]
Torq.0-nom 4-20mA
0 - Motor rated torque
[136]
Power 4-20mA
0 - Motor rated power
[137] *
Speed 4-20mA
0 - Speed High Limit (4-13 and 4-14)
[139]
Bus ctrl.
0 - 100%, (0-20 mA)
[140]
Bus ctrl. 4-20 mA
0 - 100%
[141]
Bus ctrl t.o.
0 - 100%, (0-20 mA)
[142]
Bus ctrl t.o. 4-20mA
0 - 100%
[143]
Ext. CL 1 4-20mA
0 - 100%
[144]
Ext. CL 2 4-20mA
0 - 100%
[145]
Ext. CL 3 4-20mA
0 - 100%
Values for setting the Minimum Reference is found in
open loop par. 3-02
closed loop par. 20-13
Minimum Reference/Feedb.
-
values for maximum reference for open loop is found
in par. 3-03
Maximum Reference
and for closed loop
par. 20-14
Maximum Reference/Feedb.
.
6-51 Terminal 42 Output Min Scale
Range:
Function:
0.00 %*
[0.00 - 200.00 %]
Scale for the minimum output (0 or 4mA) of the analog signal at terminal 42.
Set the value to be the percentage of the full range of the variable selected in par. 6-50
.
VLT HVAC Drive High Power Operating In-
structions
6 How to Programme
MG.11.F3.02 - VLT
®
is a registered Danfoss trademark
119
6