The number of the Active Set-up (selected as the Active Set-up in
par. 0-10
Active Set-up
) is shown. When programming in another Set-
up than the Active Set-up, the number of the Set-up being program-
med appears to the right in brackets.
The Middle section (b) shows up to 5 variables with related unit, re-
gardless of status. In case of alarm/warning, the warning is shown in-
stead of the variables.
The Bottom section (c) always shows the state of the frequency
converter in Status mode.
It is possible to toggle between three status read-out displays by press-
ing the [Status] key.
Operating variables with different formatting are shown in each status
screen - see below.
Several values or measurements can be linked to each of the displayed
operating variables. The values / measurements to be displayed can be
defined via par. 0-20
Display Line 1.1 Small
, par. 0-21
Display Line 1.2
Small
, par. 0-22
Display Line 1.3 Small
, par. 0-23
Display Line 2 Large
and par. 0-24
Display Line 3 Large
, which can be accessed via [QUICK
MENU], "Q3 Function Setups", "Q3-1 General Settings", "Q3-13 Display
Settings".
Each value/measurement readout parameter selected in par. 0-20
Dis-
play Line 1.1 Small
to par. 0-24
Display Line 3 Large
has its own scale
and number of digits after a possible decimal point. Larger numeric val-
ues are displayed with few digits after the decimal point.
Ex.: Current readout
5.25 A; 15.2 A 105 A.
Status display I:
This read-out state is standard after start-up or initialisation.
Use [INFO] to obtain information about the value/measurement linked
to the displayed operating variables (1.1, 1.2, 1.3, 2, and 3).
See the operating variables shown in the display in this illustration. 1.1,
1.2 and 1.3 are shown in small size. 2 and 3 are shown in medium size.
1.1
2
3
1.3
1.2
130BP041.10
799 RPM
Auto Remote Ramping
1 (1)
36.4 kw
7.83 A
0.000
53.2 %
Status
Status display II:
See the operating variables (1.1, 1.2, 1.3, and 2) shown in the display
in this illustration.
In the example, Speed, Motor current, Motor power and Frequency are
selected as variables in the first and second lines.
1.1, 1.2 and 1.3 are shown in small size. 2 is shown in large size.
1.1
1.2
2
1.3
130BP062.10
207RPM
Auto Remote Running
1 (1)
24.4 kW
5.25A
6.9
Hz
Status
Status display III:
This state displays the event and action of the Smart Logic Control. For
further information, see par. .
130BP063.10
778 RPM
Auto Remote Running
1 (1)
4.0 kW
0.86 A
State: 0 off 0 (off)
When: -
Do: -
Status
Display Contrast Adjustment
Press [status] and [
▲
] for darker display
Press [status] and [
▼
] for brighter display
Top section
Middle section
Bottom section
Status
43 RPM
1.4 Hz
Auto Remote Running
! Pwr.card temp (W29)
2.9%
5.44 A
25.3kW
1(1)
130BP074.10
!
Indicator lights (LEDs):
If certain threshold values are exceeded, the alarm and/or warning LED
lights up. A status and alarm text appear on the control panel.
The On LED is activated when the frequency converter receives power
from mains voltage, a DC bus terminal, or an external 24V supply. At
the same time, the back light is on.
•
Green LED/On: Control section is working.
5 How to Operate the Frequency Converter
VLT HVAC Drive High Power Operating In-
structions
84
MG.11.F3.02 - VLT
®
is a registered Danfoss trademark
5