Mains Supply 3 x 525- 690 VAC
P132
P160
P200
P250
Typical Shaft output at
550 V [kW]
110
132
160
200
Typical Shaft output at
575 V [HP]
150
200
250
300
Typical Shaft output at
690 V [kW]
132
160
200
250
Enclosure IP21
D1
D1
D2
D2
Enclosure IP54
D1
D1
D2
D2
Enclosure IP00
D3
D3
D4
D4
Output current
130BA230.10
Continuous
(at 550 V) [A]
162
201
253
303
Intermittent (60 sec over-
load)
(at 550 V) [A]
178
221
278
333
Continuous
(at 575/ 690 V) [A]
155
192
242
290
Intermittent (60 sec over-
load)
(at 575/ 690 V) [A]
171
211
266
319
Continuous KVA
(at 550 V) [KVA]
154
191
241
289
Continuous KVA
(at 575 V) [KVA]
154
191
241
289
Continuous KVA
(at 690 V) [KVA]
185
229
289
347
Max. input current
130BA229.10
Continuous
(at 550 V ) [A]
158
198
245
299
Continuous
(at 575 V) [A]
151
189
234
286
Continuous
(at 690 V) [A]
155
197
240
296
Max. cable size, mains
motor, load share and
brake [mm
2
(AWG)]
2 x 70 (2 x 2/0)
2 x 70 (2 x 2/0)
2 x 150 (2 x 300
mcm)
2 x 150 (2 x 300
mcm)
Max. external pre-fuses
[A]
1
315
350
350
400
Estimated power loss
at rated max. load [W]
4)
,
600 V
2963
3430
4051
4867
Estimated power loss
at rated max. load [W]
4)
,
690 V
3430
3612
4292
5156
Weight,
Enclosure IP21, IP 54 [kg]
96
104
125
136
Weight,
Enclosure IP00 [kg]
82
91
112
123
Efficiency
4)
0.98
Output frequency
0 - 600 Hz
Heatsink overtemp. trip
90
°
C
110
°
C
110
°
C
110
°
C
Power card ambient trip
60
°
C
VLT HVAC Drive High Power Operating In-
structions
7 General Specifications
MG.11.F3.02 - VLT
®
is a registered Danfoss trademark
171
7