4-57 Warning Feedback High
Range:
Function:
999999.999
ProcessCtr-
lUnit*
[ par. 4-56 - 999999.999 Proc-
essCtrlUnit]
Enter the upper feedback limit. When the feedback exceeds this limit, the display reads Feedb
High. The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and
on relay output 01 or 02.
4-64 Semi-Auto Bypass Set-up
Option:
Function:
[0] *
Off
No function
[1]
Enabled
Starts the Semi-Automatic Bypass set-up and continue with the procedure described above.
5-01 Terminal 27 Mode
Option:
Function:
[0] *
Input
Defines terminal 27 as a digital input.
[1]
Output
Defines terminal 27 as a digital output.
5-02 Terminal 29 Mode
Option:
Function:
[0] *
Input
Defines terminal 29 as a digital input.
[1]
Output
Defines terminal 29 as a digital output.
This parameter cannot be adjusted while the motor is running.
6.1.4 5-1* Digital Inputs
Parameters for configuring the input functions for the input terminals.
The digital inputs are used for selecting various functions in the
frequency converter. All digital inputs can be set to the following func-
tions
Digital input function
Select
Terminal
No operation
[0]
All *terminal 19, 32, 33
Reset
[1]
All
Coast inverse
[2]
27
Coast and reset inverse
[3]
All
DC-brake inverse
[5]
All
Stop inverse
[6]
All
External interlock
[7]
All
Start
[8]
All *terminal 18
Latched start
[9]
All
Reversing
[10]
All
Start reversing
[11]
All
Jog
[14]
All *terminal 29
Preset reference on
[15]
All
Preset ref bit 0
[16]
All
Preset ref bit 1
[17]
All
Preset ref bit 2
[18]
All
Freeze reference
[19]
All
Freeze output
[20]
All
Speed up
[21]
All
Speed down
[22]
All
Set-up select bit 0
[23]
All
Digital input function
Select
Terminal
Set-up select bit 1
[24]
All
Pulse input
[32]
terminal 29, 33
Ramp bit 0
[34]
All
Mains failure inverse
[36]
All
Fire mode
[37]
All
Run Permissive
[52]
All
Hand start
[53]
All
Auto start
[54]
All
DigiPot Increase
[55]
All
DigiPot Decrease
[56]
All
DigiPot Clear
[57]
All
Counter A (up)
[60]
29, 33
Counter A (down)
[61]
29, 33
Reset Counter A
[62]
All
Counter B (up)
[63]
29, 33
Counter B (down)
[64]
29, 33
Reset Counter B
[65]
All
Sleep Mode
[66]
All
Reset Maintenance Word
[78]
All
PTC Card 1
[80]
All
Lead Pump Start
[120]
All
Lead Pump Alternation
[121]
All
Pump 1 Interlock
[130]
All
Pump 2 Interlock
[131]
All
Pump 3 Interlock
[132]
All
VLT HVAC Drive High Power Operating In-
structions
6 How to Programme
MG.11.F3.02 - VLT
®
is a registered Danfoss trademark
111