5.1.8 Initialisation to Default Settings
There are two ways to initialise the frequency converter to default:
Recommended initialisation and manual initialisation.
Please be aware that they have different impact according to the below
description.
Recommended initialisation (via par. 14-22
Operation Mode
)
1.
Select par. 14-22
Operation Mode
2.
Press [OK]
3.
Select “Initialisation” (for NLCP select “2”)
4.
Press [OK]
5.
Remove power to unit and wait for display to turn off.
6.
Reconnect power and the frequency converter is reset. Note
that first start-up takes a few more seconds
7.
Press [Reset]
Par. 14-22
Operation Mode
initialises all except:
Par. 14-50
RFI Filter
Par. 8-30
Protocol
Par. 8-31
Address
Par. 8-32
Baud Rate
Par. 8-35
Minimum Response Delay
Par. 8-36
Max Response Delay
Par. 8-37
Maximum Inter-Char Delay
Par. 15-00
Operating Hours
to par. 15-05
Over Volt's
Par. 15-20
Historic Log: Event
to par. 15-22
Historic Log: Time
Par. 15-30
Alarm Log: Error Code
to par. 15-32
Alarm Log: Time
Parameters selected in par. 0-25
My Personal Menu
,
will stay present, with default factory setting.
Manual initialisation
When carrying out manual initialisation, serial com-
munication, RFI filter settings and fault log settings
are reset.
Removes parameters selected in par. 0-25
My Per-
sonal Menu
.
1. Disconnect from mains and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time
while power up for Graphical LCP (GLCP)
2b. Press [Menu] while power up for LCP 101, Numerical Dis-
play
3. Release the keys after 5 sec.
4. The frequency converter is now programmed according to
default settings
This parameter initialises all except:
Par. 15-00
Operating Hours
Par. 15-03
Power Up's
Par. 15-04
Over Temp's
Par. 15-05
Over Volt's
VLT HVAC Drive High Power Operating In-
structions
5 How to Operate the Frequency Converter
MG.11.F3.02 - VLT
®
is a registered Danfoss trademark
89
5