13-03 Reset SLC
Option:
Function:
[0]
*
Do not reset
SLC
Retains programmed settings in all
parameter group
13-** Smart Logic Control
.
[1]
Reset SLC
Resets all parameters in parameter group
13-** Smart Logic Control
to default
settings.
6.10.3 13-1* Comparators
Comparators are used for comparing continuous variables
(i.e. output frequency, output current, analog input etc.) to
fixed preset values.
Par. 13-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
130BB672.10
Illustration 6.14
In addition, there are digital values that will be compared
to fixed time values. See explanation in
13-10 Comparator
Operand
. Comparators are evaluated once in each scan
interval. Use the result (TRUE or FALSE) directly. All
parameters in this parameter group are array parameters
with index 0 to 5. Select index 0 to programme
Comparator 0, select index 1 to programme Comparator 1,
and so on.
13-10 Comparator Operand
Array [6]
Option:
Function:
Choices [1] to [31] are variables which
will be compared based on their
values. Choices [50] to [186] are digital
values (TRUE/FALSE) where the
comparison is based on the amount of
time during which they are set to
TRUE or FALSE, respectively. See
Select the variable to be monitored by
the comparator.
[0]
*
DISABLED
The comparator is disabled.
[1]
Reference
The resulting remote reference (not
local) as a percentage.
[2]
Feedback
In the unit [RPM] or [Hz]
[3]
Motor speed
[RPM] or [Hz]
[4]
Motor current
[A]
13-10 Comparator Operand
Array [6]
Option:
Function:
[5]
Motor torque
[Nm]
[6]
Motor power
[kW] or [hp]
[7]
Motor voltage
[V]
[8]
DC-link voltage
[V]
[9]
Motor thermal
Expressed as a percentage.
[10]
Drive thermal
Expressed as a percentage.
[11]
Heat sink temp.
Expressed as a percentage.
[12]
Analog input AI53 Expressed as a percentage.
[13]
Analog input AI54 Expressed as a percentage.
[14]
Analog input
AIFB10
[V]. AIFB10 is internal 10 V supply.
[15]
Analog input
AIS24V
[V] Analog input AICCT [17] [°]. AIS24V
is switch mode power supply: SMPS
24V.
[17]
Analog input
AICCT
[°]. AICCT is control card temperature.
[18]
Pulse input FI29
Expressed as a percentage.
[19]
Pulse input FI33
Expressed as a percentage.
[20]
Alarm number
The error number.
[21]
Warning number
[22]
Analog input x30
11
[23]
Analog input x30
12
[30]
Counter A
Number of counts
[31]
Counter B
Number of counts
[50]
FALSE
Enters the fixed value of false in the
comparator.
[51]
TRUE
Enters the fixed value of true in the
comparator.
[52]
Control ready
The control board receives supply
voltage
[53]
Drive ready
The frequency converter is ready for
operation and applies a supply signal
on the control board.
[54]
Running
The motor is running.
[55]
Reversing
The output is high when the
frequency converter is running counter
clockwise (the logical product of the
status bits “running” AND “reverse”)
[56]
In range
The motor is running within the
programmed current and speed
ranges set in
4-50 Warning Current Low
to
[60]
On reference
The motor is running on reference.
Parameter Descriptions
Operating Instructions VLT
®
CDS302 and CDS303
MG34M302 - VLT
®
is a registered Danfoss trademark/Commercial Compressor
85