3.4.3 CE Compliance
Fuses or circuit breakers are mandatory to comply with IEC
60364. Danfoss recommends using a selection of the
following.
The fuses below are suitable for use on a circuit capable of
delivering 100,000 Arms (symmetrical), 240V, 480V, 500V,
or 600V depending on the unit's voltage rating. With the
proper fusing, the frequency converter short circuit current
rating (SCCR) is 100,000 Arms.
Enclosure
Power
Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Max trip level
Size
[kW]
Moeller
[A]
B1
5.5-7.5
gG-25 (5.5)
gG-32 (7.5)
gG-80
PKZM4-63
63
B2
11
gG-50
gG-100
NZMB1-A100
100
B3
5.5
gG-25
gG-63
PKZM4-50
50
B4
7.5-15
gG-32 (7.5)
gG-50 (11)
gG-63 (15)
gG-125
NZMB1-A100
100
C1
15-22
gG-63 (15)
gG-80 (18.5)
gG-100 (22)
gG-160 (15-18.5)
aR-160 (22)
NZMB2-A200
160
C2
30-37
aR-160 (30)
aR-200 (37)
aR-200 (30)
aR-250 (37)
NZMB2-A250
250
C3
18.5-22
gG-80 (18.5)
aR-125 (22)
gG-150 (18.5)
aR-160 (22)
NZMB2-A200
150
C4
30-37
aR-160 (30)
aR-200 (37)
aR-200 (30)
aR-250 (37)
NZMB2-A250
250
Table 3.6 200-240 V, Frame Sizes B and C
Enclosure
Power
Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Max trip level
Size
[kW]
Moeller
[A]
B1
11-15
gG-40
gG-80
PKZM4-63
63
B2
18.5-22
gG-50 (18.5)
gG-63 (22)
gG-100
NZMB1-A100
100
B3
11-15
gG-40
gG-63
PKZM4-50
50
B4
18.5-30
gG-50 (18.5)
gG-63 (22)
gG-80 (30)
gG-125
NZMB1-A100
100
C1
30-45
gG-80 (30)
gG-100 (37)
gG-160 (45)
gG-160
NZMB2-A200
160
C2
55-75
aR-200 (55)
aR-250 (75)
aR-250
NZMB2-A250
250
C3
37-45
gG-100 (37)
gG-160 (45)
gG-150 (37)
gG-160 (45)
NZMB2-A200
150
C4
55-75
aR-200 (55)
aR-250 (75)
aR-250
NZMB2-A250
250
Table 3.7 380-500 V, Frame Sizes B and C
How to Install
Operating Instructions VLT
®
CDS302 and CDS303
30
MG34M302 - VLT
®
is a registered Danfoss trademark/Commercial Compressor
3