3.3.11 Electrical Installation, Control Cables
Terminal 37 is the input to be used for Safe Stop. Control
cables more than 100 m (330 ft) and analog signals may in
rare cases and depending on installation result in 50/60 Hz
earth loops due to noise from mains supply cables. If this
occurs, break the screen or insert a 100 nF capacitor
between screen and chassis. The digital and analog in- and
outputs must be connected separately to the frequency
converter common inputs (terminal 20, 55, 39) to avoid
ground currents from both groups to affect other groups.
3 Phase
power
input
DC bus
Switch Mode
Power Supply
Motor
Analog Output
Interface
relay1
relay2
(PNP) = Source
(NPN) = Sink
ON=Terminated
OFF=Open
Brake
resistor
130BA025.19
91 (L1)
92 (L2)
93 (L3)
PE
88 (-)
89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4-20 mA
12 (+24V OUT)
13 (+24V OUT)
37 (D IN)
18 (D IN)
20 (COM D IN)
10Vdc
15mA 130/200mA
+
-
+
-
(U) 96
(V) 97
(W) 98
(PE) 99
(COM A OUT) 39
(A OUT) 42
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
0V
5V
S801
0/4-20 mA
RS-485
RS-485
03
+10Vdc
-10Vdc -
+10Vdc
+10Vdc
0/4-20 mA
-10Vdc -
240Vac, 2A
24Vdc
02
01
05
04
06
240Vac, 2A
24V (NPN)
0V (PNP)
0V (PNP)
24V (NPN)
19 (D IN)
24V (NPN)
0V (PNP)
27
24V
0V
(D IN/OUT)
0V (PNP)
24V (NPN)
(D IN/OUT)
0V
24V
29
24V (NPN)
0V (PNP)
0V (PNP)
24V (NPN)
33 (D IN)
32 (D IN)
1
2
ON
S201
ON
2
1S202
ON/I=0-20mA
OFF/U=0-10V
95
400Vac, 2A
P 5-00
2
1
ON
S801
(R+) 82
(R-) 81
*
*
Illustration 3.24
How to Install
Operating Instructions VLT
®
CDS302 and CDS303
24
MG34M302 - VLT
®
is a registered Danfoss trademark/Commercial Compressor
3
3